VD4/R - VD4/L - VD4/R-SEC - VD4/L-SEC - INSTALLATION AND OPERATING INSTRUCTIONS 20
5.6 Characteristics of the electrical accessories
5. Product description
Shunt opening release (-M01); Additional shunt
opening release (-M02); Shunt closing release (-MC)
Electronic time delay device for undervoltage
release (installed outside the circuit breaker)
Auxiliary contacts of the circuit breaker
Rated current and breaking capacity in class
AC11 and DC11
Summary of the total quantity of auxiliary contacts available(*)
Undervoltage release (-MU)
Motor operator (-MS)
Un 
Un 
Operating limits 
Power on inrush (Ps) 
Inrush time 
Holding power (Pc) 
Opening time 
Closing time 
Insulation voltage 
Un 
Un 
Adjustable opening time
(release + time-lag device)

Un 
Rated current 
Insulation voltage 
Electrical resistance 
Un 
Un 
Operating limits:
– circuit breaker opening 
– circuit breaker closing 
Power on inrush (Ps) 
Inrush time 
Holding power (Pc) 
Opening time 
Insulation voltage 
Specifications
Un 
Un 
Operating limits 
Power on inrush (Ps) 
Rated power (Pn) 
Inrush time 
Loading time 
Insulation voltage 
Un Cosϕ T In Icu
    
    
    
    
    
Total quantity 











Standard equipment Alternative available on
request. This is the obligatory

(the additional opening
release) is also required
Alternative not available Alternative available
on request


Standard equipment Alternative available on

contacts
Alternative not available As above
(*) Each opening release required uses an auxiliary contact to shut off its power supply after having opened the circuit breaker. Thus the number of auxiliary
contacts really available diminishes in the same way as the number of opening releases installed.