The switch-disconnector is then ready to
open, also in response to fuse tripping, shunt
and undervoltage releases.
Open the switch-disconnector by turning the
operating lever 122 clockwise through
approx. 15°. Then turn the operating lever
back anti-clockwise until the stop is reached.
Observe the position indicator (see also
section 6.2.8).
3. Opening and closing of a switch-disconnector
with snap-action ON mechanism and stored-
energy spring OFF mechanism (type CS3):
Close the switch-disconnector by turning the
operating lever 122 clockwise through approx.
180° up to the stop, or open the switch-dis-
connector by turning the operating lever anti-
clockwise through approx. 180° up to the stop.
When the switch-disconnector is then ready
to open, it will also respond to fuse tripping,
shunt and undervoltage releases.
Special case:
Charge and engage the closing springs by
turning the lever anti-clockwise through approx.
180° up to the stop (pretensioning).
This action is only required:
on initial installation (stored-energy springs
then normally discharged).
for indirect operation (tripping by HRC fuse,
shunt and undervoltage release).
4. Opening and closing an integrated earthing
switch:
Switching of a normally interlocked earthing
switch is only enabled when the switch-dis-
connector is in the open position.
Close the earthing switch by turning the oper-
ating lever 122 clockwise through approx. 180°
up to the stop, or open the earthing switch by
turning the operating lever anti-clockwise
through approx. 180° up to the stop.
Observe the position indicator (see also
section 6.2.8).
5. Opening and closing with a motor-operated
mechanism:
Switch-disconnectors and earthing switches can
also be fitted with motor-operated mechanisms.
Operate the electrical control to open/close
the switch (briefly), and the switch-disconnec-
tor or earthing switch will then be switched
automatically into the opposite position, or the
stored-energy springs for the switch-dis-
connector charged.
Emergency manual operation:
If a fault occurs in the motor-operated mechanism,
the switch-disconnector and earthing switch can
be operated manually in emergencies with
operating lever 122, in a similar manner to a switch
witch manual mechanism. To disengage the
coupling to the motor-operated mechanism, first
turn the operating lever 122 up to the relevant stop
(small angle of turn).
On the next operation with the motor-operated
mechanism after its function has been restored, the
coupling automatically reengages.
Note:
The operating lever may only be fitted temporarily
for performance of an emergency manual
switching operation.
The power to the motor-operated mechanism
must be switched off for the duration of any
breakdown.
6.2.7 Insulating protection plate
(Figure 6/15)
With the isolating distance of the switch-dis-
connector open, an insulating protection plate 36
can be inserted into the relevant panel on rails.
Notes:
Always clean and inspect insulating protection
plates before use.
When moisture and dirt cause layers of foreign
matter to build up on a protection plate, there is
danger due to possible leakage currents.
Insulating protection plates are only suitable as
protection against accidental contact and not as
protection against reclosing.
The service duration of inserted protection
plates is fundamentally limited by influence of
moisture, temperature, contamination and the
adjacency of live parts.
Observe the details listed in section 7.2 with
regard to the insulating protection plates.
6.2.8 Electrical/mechanical annunciation/monitoring
When the switchgear is in operation, observe all the
operating data and condition indications in the
secondary area.
Position indicator for switch-disconnectors:
Type CK3: The switch position is identical to
the mechanism position.
Typ CR3: The switch position is not identical
to the mechanism position.
Typ CS3: The switch position is identical to
the mechanism position when
operation is direct.
For indirect operation (by fuse or
electrical release), the opening
operation results in different posi-
tions for the switch and mecha-
nism.