EasyManua.ls Logo

ABB ZS1 - Earthing and short-circuiting with the earthing cable sets; Earthing in the cable compartment; Earthing at the contact pins; Test procedures

ABB ZS1
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
50 ABB Power Distribution
6.2.9 Earthing and short-circuiting with the earthing
cable sets
(Figures 3/12, 3/13, 3/19, 6/12, 6/16 to 6/20)
1. Earthing in the cable compartment
For the earthing of the tee-off conductors, the
usual commercially available earthing bolts are
intended for use on the connecting bars and the
main earthing bar in the cable compartment.
Handling:
Use earthing cables with insulating rods in
accordance with the manufacturer’s
instructions.
Check for off-circuit condition.
Attach a warning label with an earthing symbol
to the panel door.
2. Earthing at the contact pins
An earthing system with cable cross-sections of
70 mm
2
to 150 mm
2
is also available on request,
specifically for earthing at the fixed contact pins.
a) Handling for earthing at contact pins for rated
currents up to 1250 A:
Isolate the area to be earthed and secure
against reconnection.
Remove the withdrawable circuit-breaker
part from the relevant panel.
Secure shutter 12.1 in front of the live
contact pins with padlock 130.
Bolt on actuating bars 129.1 to the shutter
operating module 129 at the required
location:
at the top to open the lower shutter,
at the bottom to open the upper shutter.
Move the shutter operating module 129
into the test/disconnected position and
completely into the service position with the
aid of hand crank 121.
Check that the area to be earthed is off-
circuit, e.g. with a high-voltage tester at the
relevant contact pins 4.1 or at the cable
terminal.
Connect the earthing cable to the fixed
earthing point.
Fit the short-circuiting cables directly onto
the contact pins using insulating rod 133.3,
and fasten them in place by turning the
insulating rod.
Attach warning label with the earthing
symbol to the panel door.
Secure neighbouring live areas (e.g.
possibly the feeder cables) to prevent
inadvertent contact.
b) Handling for earthing at contact pins for rated
currents above 1250 A:
Isolate the area to be earthed and secure
against reconnection.
Remove the withdrawable circuit-breaker
part from the relevant panel.
Secure shutter 12.1 in front of the live
contact pins with padlock 130.
Bolt on actuating bars 142.1 to the testing
and earthing module 142 at the required
location:
at the top to open the lower shutter,
at the bottom to open the upper shutter.
Fit withdrawable test and earthing part 142
with contact arms 142.2 and contact
systems 142.3 at the required positions.
Remove ball 142.4 and short-circuit bridge
142.8 if fitted.
Move the testing and earthing module 142
into the test/disconnected position and
completely into the service position with
the aid of hand crank 121.
Check that the area to be earthed is off-
circuit, e.g. with a high-voltage tester at the
relevant contact pins 142.7 or at the cable
terminal.
Connect the earthing cable to the fixed
earthing point.
Fit the short-circuiting cables to contact
pins 142.7 using insulating rod 133.3, and
fasten them in place by turning the
insulating rod.
Attach warning label with the earthing
symbol to the panel door.
Secure neighbouring live areas (e.g.
possibly the feeder cables) to prevent
inadvertent contact.
6.3 Test procedures
6.3.1 Testing the off-circuit conditon
(Figure 6/4)
The panels are fitted with a capacitive voltage
indication system including the corresponding
(hand-held) plug-in indicator for testing of the off-
circuit condition.
A distinction must be made between the low
resistance (LRM) system and the high resistance
(HR) system. For further details, see draft standard
VDE 0682 Part 415 or IEC 61243-5.
The two systems differ in several respects,
including different voltage levels which constitute
the display thresholds. The capacitive voltage

Related product manuals