48
LED presets
Only green LEDs
Only blue LEDs
Both LEDs
6. ERROR MESSAGES
Sequence F10
The temperature monitor has detected a temperature above 80° Celsius
inside the housing
The green LED flashes four times
The blue LED flashes every third and fourth time
200ms 200ms 200ms 200ms200ms200ms200ms200ms200ms200ms
1 The temperature monitor interrupts the charging
procedure. After 10 minutes, the charging proce-
dure is reinitiated automatically
2 Error code F8 is shown if the temperature inside the
housing remains at between 60° and 80° Celsius,
F8: p. 41
3 The charging procedure is reinitiated as soon as the
temperature inside the housing has fallen to below
60° Celsius
4 Ensure better cooling and/or shading of the Wall-
box. Should the error recur or persist, contact the
specialist electrical contractor to resolve the error.
Operating temperature: p. 60