Troubleshooting and Diagnostics
Fault Cause Remedy
(1)
Motor Overload fault Excessive motor load for too long Verify proper setting of P108
Verify drive and motor are proper
size for application
Flying Restart fault Controller was unable to
synchronize with the motor during
restart attempt; (P110 = 5 or 6)
Check motor / load
Single-Phase fault A mains phase has been lost Check mains voltage
Start fault Start command was present when
power was applied (P110 = 0 or 2).
Must wait at least 2 seconds
after power-up to apply Start
command
Consider alternate starting
method (see P110).
(1) The drive can only be restarted if the error message has been reset