EasyManuals Logo

AC Tech Lenze SV01B User Manual

AC Tech Lenze SV01B
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
ENGLISH
ESV251N01SXB
ESV371N01SXB
ESV751N01SXB
ESV251N02SXB
ESV371N02YXB
ESV751N02YXB
ESV112N02YXB
ESV152N02YXB
ESV222N02YXB
ESV
112N02TXB
ESV152N02TXB
ESV222N02TXB
ESV402N02TXB
ESV552N02TXB
ESV752N02TXB
6
Technical data
2.2 Ratings
120VAC Doubler / 240VAC Models
Type Power
[Hp/kW]
Mains Output Current
Watts
Loss
Voltage
(1)
I
in
(120V) I
in
(240V) I
n
CLim
max
(2)
0.33 / 0.25
120 V Single-phase (1/N/PE)
(90 …
132 V)
OR
240 V Single-phase (2/PE)
(170 … 264 V)
6.8 3.4 1.7 200 24
0.5 / 0.
37 9.2 4.
6 2.4 200 32
1 / 0.75 16.6 8.3 4.2 200 52
240VAC Models
Type Power
[Hp/kW]
Mains Output Current
Watts
Loss
Voltage
(1)
I
in
1~ (2/PE) I
in
3~ (3/PE) I
n
CLim
max
(2)
0.33 / 0.25
240 V Single Phase (2/PE)
3
.4
- 1
.7 200 20
0.5 / 0.37
240 V Single-phase (2/PE)
OR
240 V Three-phase (3/PE)
(170 … 264 V)
5.1 2.9 2.4 200 27
1
/ 0.75 8.8 5.0 4.2 200 4
1
1.5 / 1.1 12.0 6.9 6.0 200 6
4
2 / 1.5 13.3 8.1 7.0 200 75
3
/ 2.2 17.1 10.8 9.6 200 1
03
1.5 / 1.1
240 V Three-phase (3/PE)
(
170 V … 264 V)
- 6
.9 6.0 200 64
2 / 1.5 - 8.
1 7.0 200 75
3 / 2.2 - 1
0.8 9.6 200 103
5 / 4.0 - 1
8.6 16.5 200 154
7.5 / 5.5 - 2
6 23 200 225
10 / 7.5 - 33 29 200 274
(1) Frequency Range: 48 Hz … 62 Hz
(2) Current Limit (CLim) is a percentage of the output current, I
n
. CLim
max
is the maximum setting for P171.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AC Tech Lenze SV01B and is the answer not in the manual?

AC Tech Lenze SV01B Specifications

General IconGeneral
BrandAC Tech
ModelLenze SV01B
CategoryInverter
LanguageEnglish