General Error Code
No signal
detected on main
hall sensor
Check & fix connection between
main hall sensor and PCBA.
No signal
detected on sub
hall sensor
-Check & fix connection between
sub hall sensor and PCBA.
-Power off and restart the device
Sub hall count
faster than main
hall
Main hall sensor and
sub hall sensor wire
switched
Swap main hall sensor and sub hall
sensor wire on PCBA, learn travel
limit again.
Wicket door
terminal open
circuit
-Wicket door is open
-Wicket door
connecting wire is loose
-Wicket door terminals
are loose
-Close the wicket door
-Fasten the wicket door connecting
wire
-Fasten the wicket door terminals
-Incorrect type motor is
used
-Motor is damaged
-Replace with a correct type motor
-Replace with a new motor
Door blocked
during closing
-There's object under
the door
-Stuck between door
track and door
-Move away object under the door
-Adjust door installation & reset
travel limit