The first group of other alarm settings: refer to Phase A overcurrent alarm
Phase B overcurrent alarm
Phase C overcurrent alarm
Maximum overcurrent alarm
Neutral overcurrent alarm
Phase A undercurrent alarm
Phase B undercurrent alarm
Phase C undercurrent alarm
Minimum undercurrent alarm
Neutral undercurrent alarm
Maximum current unbalance
alarm
Phase A overvoltage alarm
Phase B overvoltage alarm
Phase C overvoltage alarm
Maximum phase overvoltage
alarm
AB line overvoltage alarm
BC line overvoltage alarm
CA line overvoltage alarm
Maximum line overvoltage alarm
Phase A undervoltage alarm
Phase B undervoltage alarm
Phase C undervoltage alarm
Minimum phase undervoltage
AB line undervoltage alarm
Current Demand MAX, Phase B
Current Demand MAX, Phase C
Active Power Demand , Total
Reactive Power Demand , Total
Used to set the alarm value and read the alarm
record value. If the current coefficient is -3,
the Phase A overcurrent alarm action value
(register 1301) is set to 6000, then the actual
alarm value is 6000*10^(-3) = 6.000A
Neutral current coefficient
The first group of alarms: Phase A
overcurrent alarm
When Bit0 is 1, the alarm is enabled, when
Bit0 is 0, the alarm is disabled;
When Bit1 is 1, the zero-value alarm is
disabled, when Bit1 is 0, the zero-value
alarm is enabled.
Primary. Range: 0 ~ 9999. If the current
coefficient is -3, Phase A overcurrent alarm
action value is set to 6000, then the actual
alarm value is 6000*10^(-3) = 6.000A,other
situation is similar..