57
current alarm
1960
Over total harmonic of Phase B
current alarm
1965
Over total harmonic of Phase C
current alarm
1970
Over total harmonic of Phase A
voltage alarm
1975
Over total harmonic of Phase B
voltage alarm
1980
Over total harmonic of Phase C
voltage alarm
1985
Over total even harmonic of Phase
A current alarm
1990
Over total even harmonic of
Phase B current alarm
1995
Over total even harmonic of
Phase C voltage alarm
2000
Over total even harmonic of Phase
A voltage alarm
2005
Over total even harmonic of
Phase B voltage alarm
2010
Over total even harmonic of
Phase C voltage alarm
2015
Over total odd harmonic of Phase
A current alarm
2020
Over total odd harmonic of Phase
B current alarm
2025
Over total odd harmonic of
Phase C current alarm
2030
Over total odd harmonic of Phase
A voltage alarm
2035
Over total odd harmonic of Phase
B voltage alarm
2040
Over total odd harmonic of
Phase C voltage alarm
2045
Over total demand of active power
alarm
2050
Under total demand of active
power alarm
2055
Reverse phase sequence alarm
2060
DI1 digital input alarm
2065
DI2 digital input alarm
2070
DI3 digital input alarm
2075
DI4 digital input alarm
2080
1
st
way temp alarm
2085
2
nd
way temp alarm
2090
3
rd
way temp alarm
2095
4
th
way temp alarm
Note: The action value of unbalance is the register value *0.1%, the action value of power factor is the register value *0.001, the action
value of harmonic alarm is the register value *0.01%, and the action value of frequency alarm is the register value *0.01Hz.
Other event records: Refer to event record 1
2204
Event record 2
2208
Event record 3
2212
Event record 4
2216
Event record 5
2220
Event record 6
2224
Event record 7
2228
Event record 8
2232
Event record 9
2236
Event record 10
2240
Event record
11
2244
Event record
12
2248
Event record
13
2252
Event record 14
2256
Event record 15
2260
Event record
16
Note: To read the most recent 128 event records, you can read the register 20000-20513, refer to the format of register 2200-2203.
Register
(WORD)
Description
Unit
Data Type
Note
2200
Event record 1
UInt16 (RO)
When Bit15 is 1, it means DI. When it is 0, it
means DO.
When Bit14 is 1, it means ON. When it is 0, it
means OFF.
Low byte indicates DI/DO number
2201
YearMonth
UInt16 (RO)
High byte:Year; Low byte: Month
2202
DayHour
UInt16 (RO)
High byte: Day ; Low byte: Hour
2203
Minute second
UInt16 (RO)
High byte:Year; Low byte: Month
Register
(WORD)
Name
Resoluti
on
Data(Read
and write
attribute)
Remarks
2280
1ST group alarm state
UInt16 (RO)
Bit0-bit15 (the lowest digit is Bit0) corresponds
to alarm number 0-15.For example: BIT0
corresponds to A phase overcurrent alarm, and so
on