66
Other settings of transmission output: refer to setting of the 1st transmission output
Setting of the 2nd transmission
output
Setting of the 3rd transmission
output
Setting of the 4th transmission
output
Total RMS value of phase A
fundamental voltage
Total RMS value of phase B
fundamental voltage
Total RMS value of phase C
fundamental voltage
Total RMS value of Phase A
harmonic current
Total RMS value of Phase B
harmonic current
Total RMS value of Phase C
harmonic current
Total RMS value of Phase A
harmonic voltage
Total RMS value of Phase B
harmonic voltage
Total RMS value of Phase C
harmonic voltage
Setting of
the 1st
transmissi
on output
Transmission type
and signal
selection
High byte:
Transmission type
(1:4-20mA,
2:0-20mA, 3:1-5V,
4:0-5V)
Low Byte: Signal
Selection (Refer to
Table 3 in 7.5
System Setup -
Analog Output
Settings)
For example: 4-20mA is
selected for the
transmission type, and
phase A current is selected
for the signal. The
corresponding value of
the high point is 5000,
and the corresponding
value of the low point is
0, and the actual decimal
point of the current
display is 3 bits.
When the actual current
value of phase A is
5.000A, the transmission
output is 20mA. When
the actual current value of
phase A current is 0, the
output is 4 mA. When
the actual current value of
phase A is 2.500 A, the
transmission output is 12
mA.
Corresponding value
of the high point
Corresponding value
of the low point