68
Other settings of analog input: Refer to the 1st analog input settings
5603
Setting of the 2nd analog input
5606
Setting of the 3rd analog input
5609
Setting of the 4th analog input
5612
Setting of the 5th analog input
5615
Setting of the 6th analog input
5618
Setting of the 7th analog input
5621
Setting of the 8th analog input
5624
Setting of the 9th analog input
5627
Setting of the 10th analog input
5630
Setting of the 11th analog input
5633
Setting of the 12th analog input
5636
Setting of the 13th analog input
5639
Setting of the 14th analog input
5642
Setting of the 15th analog input
5645
Setting of the 16th analog input
5648
Setting of the 17th analog input
5651
Setting of the 18th analog input
5654
Setting of the 19th analog input
5657
Setting of the 20th analog input
5660
Setting of the 21st analog input
5663
Setting of the 22nd analog input
5666
Setting of the 23rd analog input
5669
Setting of the 24th analog input
5672
Setting of the 25th analog input
5675
Setting of the 26th analog input
5678
Setting of the 27th analog input
5681
Setting of the 28th analog input
5684
Setting of the 29th analog input
5687
Setting of the 30th analog input
5690
Setting of the 31st analog input
5693
Setting of the 32nd analog input
Note: 1. Read-write property: "RO" is read-only, parameter is read with 0X03H command; "R/W" is readable and writable, and system
parameter is written with 0X10H command. Do not write data to unlisted or unwritable Address.
2
For Int32 type data, the high bits are in the front and the low bits are in the back
2. Correspondence between communication value and actual value
It is agreed that Val_t is the communication readout value and Val_s is the actual value.
2.1 Voltage, Current, Power Factor, Frequency, Unbalance (Secondary)
The series of measured values are read with 03 command of the Modbus-RTU communication protocol. Each item occupies 1
word. The correspondence between the communication value and the actual secondary measurement value is shown in the following
table:
For example: To read phase A voltage Uan, the data can be read at address 243 in Int16eger reading mode by MODSCAN, the
communication read-out value Val_t is 2200,then Val_t = 2200*0.1=220V.
2.2 Voltage, Current, Power Factor, Frequency, Unbalance (Primary)
The series of measured values are read with 03 command of the Modbus-RTU communication protocol. The voltage and current
occupy 2 words, and the power factor, frequency, and unbalance occupy 1 byte. The correspondence between the communication value
and the actual secondary measurement value is shown in the following table:
Register
(WORD)
Description
Unit
Data Type
Note
5696-5727
Inverse value of No.1-32 analog
Input
Int16 (RO)
Inverse value of No.1-32 analog Input
5728-5759
The actual value of No.1-32
analog Input
0.001
Int16 (RO)
The unit is mA when the input selection is
4-20mA or 0-20mA, and the unit is V when 1-5V
or 0-5V is selected.
Applicable parameters
Resolution
Correspondence
Unit
Voltage ,Uan
Ubn
Ucn
Uab
Ubc
Uca
0.1V
Val_s
Val_t*0.1
V
Current ,I
A
I
B
I
C
0.001A
Val_sVal_t*0.001
A
Power factor, PF
A
PF
B
PF
C
PF
0.001
Val_sVal_t*0.001
No unit
Frequency, F
0.01Hz
Val_sVal_t*0.01
Hz
Unbalance ,I(ubl)
ULL(ubl),ULN(ubl)
0.1
Val_s
Val_t*0.1
%
Applicable parameters
Resolution
Correspondence
Unit
Voltage,UanUbnUcnUabUbcUca
0.1V
Val_sVal_t*0.1
V