EasyManuals Logo

Acson A5LC20CR User Manual

Acson A5LC20CR
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
1-6
Fan Coil Unit 5WMWS20GR 5WMWS20GR 5WMWS25GR
Water Source Heat Pump Unit 5WSS16AR 5WSS20AR 5WSS25AR
Nominal Cooling Capacity Btu/h 15400 20000 25000
W 4505 5848 7450
Nominal Heating Capacity Btu/h 14800 21000 25000
W 4327 6298 7448
Unit Weight kg/lb 16 / 35.27
Fan Motor Permanent Split Capacitor
Fan Blower
Air Flow Rate (High Speed) m
3
/min 510 / 240.72 650 / 306.77
Refrigerant Circuit
Liquid valve connection mm/in 6.35 / 1/4
Gas valve connection mm/in 12.7 / 1/2 15.88 / 5/8
Drain Pipe Connection mm/in 20 / 0.79
Air Filter SARANET + IONIZER + DEODORIZER
ELECTRICAL AND WIRING
Fan Coil Unit 5WMWS10GR 5WMWS10GR 5WMWS15GR
Water Source Heat Pump Unit 5WSS07AR 5WSS10AR 5WSS15AR
Power Supply V/Ph/Hz 230 / 1/50
Voltage Range V 220 ~ 240
Nominal Power Input (Cooling) W 528 668 945
Nominal Power Input (Heating) W 538 688 935
Nominal Current (Cooling) A 2.41 2.91 4.53
Nominal Current (Heating) A 2.41 3.00 4.43
Capacitor (440 VAC) µf 1.0 µF 400 VAC
Electrical Data
Fan Coil Unit 5WMWS20GR 5WMWS20GR 5WMWS25GR
Water Source Heat Pump Unit 5WSS16AR 5WSS20AR 5WSS25AR
Power Supply V/Ph/Hz 230 / 1/50
Voltage Range V 220 ~ 240
Nominal Power Input (Cooling) W 1030 1420 1513
Nominal Power Input (Heating) W 990 1570 1663
Nominal Current (Cooling) A 4.6 6.3 6.8
Nominal Current (Heating) A 4.5 7.0 7.5
Capacitor (440 VAC) µf 2.0 µF 440 VAC
Model 5WMWS10/15GR 5WMWS20/25GR
Coupling Unit 5WSS 5LC 5WSS 5LC
07/10/15AR 07/10/15CR 16/20/25AR 20/25CR
Voltage Range 220 ~ 240V /1Ph /50Hz + !
Power Supply Cable Size* mm
2
1.5 1.5 2.5 2.5
Number of Wire 3 3 3 3
Interconnection Cable Size* mm
2
1.5 1.5 2.5 2.5
Number of Wire 3 4 3 4
Recommended Fuse A 15 15 20 20
RECOMMENDED CABLE SIZES
IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected to
comply with the local/national codes of regulations. This is also subjected to the type of installation and
conductors used.