EasyManuals Logo

Acson A5WM 15GR User Manual

Acson A5WM 15GR
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #132 background imageLoading...
Page #132 background image
130
Diagnostic Guidelines
By means of pressure reading:
Pressure
Data
Circuit
Too low
A little low
Normal
A little high
Too high
Probable cause
High side
Low side
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. air)
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
High side
Low side
1. Poor compression / no compression (compressor
defective)
2. Reversing valve leaking.
High side
Low side
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air filter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
5. Defective defrost control, outdoor coil freeze up (heating).
6. Outdoor fan locked / seized (heating).
High side
Low side
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Indoor fan locked / seized (heating).
4. Indoor air filter clogged / dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air)
High side
Low side
1. Air intake temperature of indoor unit too high.
Downloaded from AC-Manual.com Manuals

Other manuals for Acson A5WM 15GR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Acson A5WM 15GR and is the answer not in the manual?

Acson A5WM 15GR Specifications

General IconGeneral
BrandAcson
ModelA5WM 15GR
CategoryAir Conditioner
LanguageEnglish

Related product manuals