TECHNICAL SPECIFICATION
TS-SB-B/D-AM-A1
15
Cable Size
Model
Indoor
ADB40B
ADB40B
ADB50B
Outdoor
ALC35D
ALC40D
ALC50D
Voltage Range**
Indoor
220 - 240V /1Ph /50Hz + N +
Outdoor
380 - 415V /3Ph /50Hz + N +
Power supply cable size*
A) Indoor
mm²
1
1
1
B) Outdoor
mm²
1
1
1
C) Total
mm²
1
1
1
Number of Conductors
A) Indoor
-
-
-
B) Outdoor
5
5
5
Interconnection cable size*
mm²
1
1
1
Number of Conductors
4
4
4
Recommended fuse/circuit breaker rating*
A) Indoor
A
2
2
6
B) Outdoor
A
12
12
16
C) Total
A
16
16
20
Model
Indoor
ADB60B
ADB80B
ADB80B
Outdoor
ALC61D
AMC72C
AMC80C
Voltage Range**
Indoor
220 - 240V /1Ph /50Hz + N +
Outdoor
380 - 415V /3Ph /50Hz + N +
Power supply cable size*
A) Indoor
mm²
1
1
1
B) Outdoor
mm²
1
2.5
2.5
C) Total
mm²
1.5
2.5
2.5
Number of Conductors
A) Indoor
-
-
-
B) Outdoor
5
5
5
Interconnection cable size*
mm²
1
1
1
Number of Conductors
4
4
4
Recommended fuse/circuit breaker rating*
A) Indoor
A
6
6
6
B) Outdoor
A
20
25
32
C) Total
A
20
25
32
Model
Indoor
ADB100B
ADB100B
Outdoor
AMC100B
AMC100C
Voltage Range**
Indoor
220 - 240V /1Ph /50Hz + N +
Outdoor
380 - 415V /3Ph /50Hz + N +
Power supply cable size*
A) Indoor
mm²
1
1
B) Outdoor
mm²
4
4
C) Total
mm²
4
4
Number of Conductors
A) Indoor
-
-
B) Outdoor
5
5
Interconnection cable size*
mm²
1
1
Number of Conductors
4
4
Recommended fuse/circuit breaker rating*
A) Indoor
A
16
16
B) Outdoor
A
32
32
C) Total
A
40
40