TECHNICAL SPECIFICATION
TS-SB-B/D-AM-A1
24
Indoor
Sound Power Level
Model Speed
1/1 Octave Sound Power Level (dB) ref 1pW
Overall
(dBA)
125Hz
250Hz
500Hz
1kHz
2kHz
4kHz
8kHz
*ADB40B
High
63
65
66
65
61
59
53
69
Med
63
63
65
64
60
59
52
68
Low
62
61
64
62
58
56
50
66
*ADB50B
High
66
65
66
66
62
60
54
70
Med
65
63
66
64
61
59
53
69
Low
63
62
65
63
60
58
51
68
*ADB60B
High
75
71
75
74
71
70
66
79
Med
76
68
71
70
67
66
61
75
Low
78
66
69
67
64
63
57
72
*ADB80B
High
68
67
70
69
64
62
54
73
Med
69
64
68
68
61
59
60
70
Low
66
62
66
63
58
56
46
67
*ADB100B
High
74
72
74
73
66
65
59
77
Med
73
70
73
71
64
62
55
75
Low
70
68
71
68
60
59
49
72
*ADB125B
High
75
76
78
70
69
62
58
78
*ADB150B1
High
74
77
78
75
72
69
63
80
*ADB200B2
High
83
84
83
81
77
73
68
85
ADB250B2
High
85
86
85
83
79
75
70
87
ADB300B2/B3
High
87
88
87
85
81
77
72
89
ADB350B3
High
90
91
90
87
84
80
75
92
ADB400B4
High
88
89
88
86
82
78
73
90
ADB450B3
High
91
92
91
89
85
81
76
93
ADB500B4
High
94
95
94
92
88
84
79
96
ADB600B4
High
87
88
87
85
81
77
72
89
ADB750B5
High
91
92
91
89
85
81
76
93
*Remarks: Test with 5ft length discharge duct, terminated flush with the internal wall of reverberation room.