EasyManua.ls Logo

Acson ADB-B Series - Page 21

Acson ADB-B Series
189 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TECHNICAL SPECIFICATION
TS-SB-B/D-AM-A1
19
Model
Indoor
ADB200B2
ADB250B2
ADB300B2
Outdoor
A4MC100D
x 2
A4MC125D
x 2
A4MC150D
x 2
Voltage Range**
Indoor
380 - 415V /3Ph /50Hz + N +
Outdoor
380 - 415V /3Ph /50Hz + N +
Power supply cable size*
A) Indoor
mm²
1
1
1
B) Outdoor
mm²
4
4
6
C) Total
mm²
10
16
25
Number of Conductors
A) Indoor
5
5
5
B) Outdoor
5
5
5
Interconnection cable size*
mm²
1
1
1
Number of Conductors
1 x 2
1 x 2
1 x 2
Recommended fuse/circuit breaker rating*
A) Indoor
A
10
16
16
B) Outdoor
A
32
40
50
C) Total
A
63
80
125
Model
Indoor
ADB300B3
ADB350B3
Outdoor
A4MC100D
x 3
A4MC100D
x 1
A4MC125D
x 2
Voltage Range**
Indoor
380 - 415V /3Ph /50Hz + N +
Outdoor
380 - 415V /3Ph /50Hz + N +
Power supply cable size*
A) Indoor
mm²
1
1.5
B) Outdoor
mm²
4
4
C) Total
mm²
25
25
Number of Conductors
A) Indoor
5
5
5
B) Outdoor
5
5
5
Interconnection cable size*
mm²
1
1
1
Number of Conductors
1 X 3
1
1 X 2
Recommended fuse/circuit breaker rating*
A) Indoor
A
16
20
B) Outdoor
A
32
32
C) Total
A
100
125
Model
Indoor
ADB400B4
ADB450B3
ADB500B4
ADB600B4
Outdoor
A4MC100D
x 4
A4MC150D
x 3
A4MC125D
x 4
A4MC150D
x 4
Voltage Range**
Indoor
380 - 415V /3Ph /50Hz + N +
Outdoor
380 - 415V /3Ph /50Hz + N +
Power supply cable size*
A) Indoor
mm²
1
1.5
2.5
4
B) Outdoor
mm²
4
6
4
6
C) Total
mm²
35
50
50
70
Number of Conductors
A) Indoor
5
5
5
5
B) Outdoor
5
5
5
5
Interconnection cable size*
mm²
1
1
1
1
Number of Conductors
1 X 4
1 X 3
1 X 4
1 X 4
Recommended fuse/circuit breaker rating*
A) Indoor
A
20
25
32
32
B) Outdoor
A
32
50
40
50
C) Total
A
150
175
175
200

Related product manuals