EasyManua.ls Logo

Acson ADB-B Series - Page 20

Acson ADB-B Series
189 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TECHNICAL SPECIFICATION
TS-SB-B/D-AM-A1
18
Model
Indoor
ADB75D
ADB100D
Outdoor
A4MC75D
A4MC100D
Voltage Range**
Indoor
220 - 240V /1Ph /50Hz + N +
Outdoor
380 - 415V /3Ph /50Hz + N +
Power supply cable size*
A) Indoor
mm²
1
1
B) Outdoor
mm²
2.5
4
C) Total
mm²
2.5
4
Number of Conductors
A) Indoor
-
-
B) Outdoor
5
5
Interconnection cable size*
mm²
1
1
Number of Conductors
4
4
Recommended fuse/circuit breaker rating*
A) Indoor
A
6
16
B) Outdoor
A
32
32
C) Total
A
32
40
Model
Indoor
ADB125D
ADB150D1
ADB150D2
Outdoor
A4MC125D
A4MC150D
A4MC75D x 2
Voltage Range**
Indoor
380 - 415V /3Ph /50Hz + N +
Outdoor
380 - 415V /3Ph /50Hz + N +
Power supply cable size*
A) Indoor
mm²
1
1
1
B) Outdoor
mm²
4
6
2.5
C) Total
mm²
4
6
10
Number of Conductors
A) Indoor
3
3
5
B) Outdoor
5
5
5
Interconnection cable size*
mm²
1
1
1
Number of Conductors
4
4
1 X 2
Recommended fuse/circuit breaker rating*
A) Indoor
A
6
6
6
B) Outdoor
A
40
50
25
C) Total
A
40
50
50
Model
Indoor
ADB200D2
ADB300D2
ADB400D4
ADB500D4
Outdoor
A4MC100D
x 2
A4MC150D
x 2
A4MC100D
x 4
A4MC125D
x 4
Voltage Range**
Indoor
380 - 415V /3Ph /50Hz + N +
Outdoor
380 - 415V /3Ph /50Hz + N +
Power supply cable size*
A) Indoor
mm²
1
1
1.5
4
B) Outdoor
mm²
2.5
6
2.5
4
C) Total
mm²
10
25
35
50
Number of Conductors
A) Indoor
5
5
5
5
B) Outdoor
5
5
5
5
Interconnection cable size*
mm²
1
1
1
1
Number of Conductors
1 x 2
1 x 2
1 X 4
1 X 4
Recommended fuse/circuit breaker rating*
A) Indoor
A
12
20
20
40
B) Outdoor
A
32
50
32
40
C) Total
A
63
100
150
175

Related product manuals