Adtech CNC Technology Co., Ltd. 11. System parameters
- 75 -
Note : Output terminal No. configuration is same as input terminal
configuration. Output terminal No. and wire No. are mapped
063 Safe Signal
… …
087 TCheck Limit DetectPort
Range : 0~23
Unit : Terminal No.
Authority : Super Admin
Default : The port table in the manual
Effective time : Instant
Note : System functions correspond to assigned terminal No.;
Terminal No. is also set by parameter 15~62, and mapped to specified
wire No.;
To shield this function, you can type 8888 and press Insert. This
operation is in background, and displays “255” if the operation is
successful.
083 IO Conf in RESET 00~15
084 IO Conf in RESET 16~23
Range : 0~65535
Unit :
Authority : Super Admin
Default : 65404
243
Effective time : Instant
Note : Used to configure the IO signal that the system needs to reset when there
is alarm.
Use binary system to configure in positions.
For example: 83:65404, is 1111 1111 0111 1100 in binary system;
Which indicates that port 0, 1 and 7 won’t be reset due to system pause
or alarm.