EasyManuals Logo

Advantech ADAM-4017 User Manual

Advantech ADAM-4017
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #209 background imageLoading...
Page #209 background image
Chapter 4 Command Set 4-125
Chapter 4
4016
$AAA
Name Zero Calibration
Description Stores the voltage output value of the addressed strain gauge
input module as zero voltage reference.
Syntax $AAA(cr)
$ is a delimiter character.
AA(range 00-FF) represents the 2-character hexadecimal
address of the strain gauge input module whos output channel
is to be calibrated.
A is the zero calibration command.
(cr) is the terminating character, carriage return (0Dh)
Response !AA(cr) if the command is valid.
?AA(cr) if an invalid command was issued.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
! delimiter character indicating a valid command was received.
? delimiter character indicating the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the strain gauge input module.
(cr) is the terminating character, carriage return (0Dh)
Before issuing the Zero Calibration command, the analog output should be
trimmed to the correct value with the Trim Calibration command. A
voltmeter should be connected to the modules output channel.(See also
the strain gauge input modules Trim Calibration command and Chapter 5,
Calibration, for a detailed description.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech ADAM-4017 and is the answer not in the manual?

Advantech ADAM-4017 Specifications

General IconGeneral
BrandAdvantech
ModelADAM-4017
CategoryControl Unit
LanguageEnglish

Related product manuals