4-126 ADAM 4000 Series User's Manual
Command Set
4016
$AAB
Name Span Calibration
Description Stores the voltage output value of the addressed strain gauge
input module as 10V reference.
Syntax $AAB(cr)
$ is a delimiter character.
AA(range 00-FF) represents the 2-character hexadecimal
address of the strain gauge input module whos output channel
is to be calibrated.
B is the span calibration command.
(cr) is the terminating character, carriage return (0Dh)
Response !AA(cr) if the command is valid.
?AA(cr) if an invalid command was issued.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
! delimiter character indicating a valid command was received.
? delimiter character indicating the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the strain gauge input module.
(cr) is the terminating character, carriage return (0Dh)
Before issuing the Span Calibration command, the analog output should be
trimmed to the correct value with the Trim Calibration command. A
voltmeter should be connected to the modules output channel.(See also
the strain gauge input modules Trim Calibration command and Chapter 5,
Calibration, for a detailed description.)