17
General data
Classification VFI SS 211 acc. to IEC 62040–3
Double conversion technology
Overall efficiency AC-AC (full load)
PROTECT C. 1000 (S)
85 %
PROTECT C. 2000 (S)
85 %
PROTECT C. 3000 (S)
88 %
Noise level (1m distance)
PROTECT C. 1000 (S) < 45 dB (A)
PROTECT C. 2000 (S) < 50 dB (A)
PROTECT C. 3000 (S) < 50 dB (A)
Type of cooling Forced cooling
by variable speed fans
Operating temperature range 0°C to +40°C
Recommendation +15°C to
+25°C (due to battery
system)
Storage temperature range 0°C to +40°C
Relative humidity < 95%, non-condensing
Max. site altitude up to 1000 m above sea level
If the UPS is installed or used
in a place where the altitude is
above than 1000m, the output
power has to be reduced:
Outlets
PROTECT C. 1000 (S) 4 x IEC 320-10A
PROTECT C. 2000 (S) 6 x IEC 320-10A
PROTECT C. 3000 (S) 4 x IEC 320-10A
+ 1 x IEC 320-16A
Equipment colour Black line
Altitude (m) 1000 1500 2000 2500 3000
Derating Power 100% 95% 90% 85% 80%