AM Series Boilers and Water Heaters
CHAPTER 9 OPERATION
OMM-0100_0D AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 103 of 154
GF-146 Ph.: 800-526-0288 03/28/16
9.17 Factory Menu
Inappropriate changes to parameters in the Factory Menu could result in a unit or system
malfunction. For this reason, only a qualified technician who has in-depth knowledge of the unit
should make any changes to the parameters in this menu. The parameters available allow the
unit to be configured and set for proper operation.
The Factory Menu for boilers and water heaters are different from one another, so there are
separate columns showing the settings for each in the chart below.
To enter the Factory Menu, perform the following steps:
Factory Menu Navigation and Adjustment
1. Turn the electrical power switch to OFF.
2. Simultaneously press and hold the RESET and buttons.
3. While the RESET and buttons are both depressed, turn the power switch to ON.
4. Wait until the word “init” is displayed in the control panel display, or until the control panel
display begins to show the 3000 parameters, then release the RESET button and then the
button.
5. Press the and buttons to scroll up or down through the parameters.
6. To change a displayed parameter, press the RESET button. The parameter value will blink.
7. Press the and buttons to cycle up or down through the parameter values.
8. To set a parameter value, press the RESET button while the desired value is displayed.
9. Wait at least 10 seconds after the last parameter change before exiting menu.
10. Exit the menu by turning the unit power switch to OFF.
11. The power switch may now be turned ON, and the Factory Menu will no longer be
displayed.
Factory Menu
BOILER
PARAMETERS
WATER HEATER
PARAMETERS
PARA#
PARAMETER
DESCRIPTION
RANGE
FACTORY
SETTINGS
BURNER
1
BURNER
2 TO 4
BURNER
1
BURNER
2 TO 4
3001
Burner logic address
NOTE: This is NOT
the
Modbus address
0 = No cascade
1 = Burner 1 (Master)
2 to 4 = Burner
2 to 4 (slave burners)
2
1 2 to 4
1 2 to 4
3002
Fan speed range 0 to 4 0
Refer to Table 8-1 in Chapter 8
3003
Display units
C = °C and bar units
F = °F and PSI units
F
F F
F F

Table of Contents

Other manuals for Aerco AM 750B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aerco AM 750B and is the answer not in the manual?

Aerco AM 750B Specifications

General IconGeneral
BrandAerco
ModelAM 750B
CategoryBoiler
LanguageEnglish

Related product manuals