INSTALLATION MANUAL
CHILLERS
REVERSIBLE HEAT PUMPS
CONDENSING UNITS
• EXTERNAL UNITS
HIGH EFFICIENCY
HOT WATER PRODUCTION UP TO 50 °C
Aermec
participates in the EUROVENT Programme: LCP.
The products of interest can be found on:
www.eurovent-certification.com
EN
ANL
ANL-H
020-202
Question and Answer IconNeed help?

Do you have a question about the AERMEC ANL 020 and is the answer not in the manual?

AERMEC ANL 020 Specifications

General IconGeneral
BrandAERMEC
ModelANL 020
CategoryChiller
LanguageEnglish

Summary

General Instructions for the Installer

Conservation of Documentation

Submit manual with supplementary documentation to the system user for future reference.

Safety Instructions and Installation Standards

Install equipment by qualified technician per national legislation. Read instructions and minimize risks.

Selection and Position of Installation

Positioning Guidelines

Verify lifting capability, use appropriate methods for moving units, and secure the unit level.

System Example for DHW Production

System Charging Procedure

System Draining Procedure

Electrical Connections and Requirements

Mandatory Electrical Requirements

Ensure proper circuit breaker, earth connection, and correct phasing for three-phase units.

Checks and First Start-Up

Preparing for First Start-Up

Ensure all works are completed before start-up. Free start-up may be available.

Preliminary Checks Before Powering Up

Verify safety precautions, unit fixing, clearances, cable sizing, and connections.

Checks to be Done When Powered Up

Check power supply voltages, installer connections, and compressor crankcase heater operation.

Hydraulic Circuit Checks

Verify hydraulic connections, pump operation, flow rate, and flow switch function.

Refrigerant Circuit Checks

Check compressor current, noise, voltage, phase imbalance, leaks, superheat, and discharge temperature.

Safety and Control Devices Checks

Test high pressure pressostat and anti-freeze protection.

Operating Characteristics

Cooling Setpoint

Factory default cooling setpoint is 7°C with a 5K differential.

Heating Setpoint

Factory default heating setpoint is 45°C with a 5K differential.

Compressor Delay Timers

Timers prevent excessive compressor starts, with minimum stop/start delays.

Circulating Pumps Operation

System pump starts immediately; flow switch control enables after 30 seconds.

Anti-Freeze Alarm

Alarm triggers if water temp drops below 3°C; requires manual reset and specific service.

Water Flow Alarm

Activates if water flow is insufficient after 30 seconds, stopping compressors and pump.

Routine Maintenance Checks

Hydraulic Circuit Maintenance

Check water circuit filling, filter, flow switch, air absence, flow rate, insulation, and antifreeze.

Electric Circuit Maintenance

Check safeties, power supply voltage, input, connections, and crankcase heater.

Refrigerant Circuit Maintenance

Check heat exchanger, compressors, pressures, leaks, pressure switches, and filter drier.

Mechanical Checks

Tighten screws, check unit structure, and treat any signs of corrosion.

Special Maintenance and Disposal

Special Maintenance

Address refrigerant leaks, repair, and recharge unit according to legislation and practices.

Disposal Procedures

Ensure unit disposal is carried out in accordance with current legal requirements.

Procedure for Selection of System Type

How to Modify a User Menu Parameter

Access USER setting, enter password 000, navigate parameters, modify values, and confirm.

How to Modify an Installer Menu Parameter

Access INSTALLER menu with password 030, navigate parameters, modify values, and confirm.