EN
21.11 - 6755517_05
14
TECHNICAL DATA MODELS POWER SUPPLY M.U. ANL100 ANL150
IP PROTECTION
IP Alls - - 24 24
SCROLL COMPRESSORS
Alls -
Resistance sump compressor Alls - 2 x 35 2 x 35
Capacity controls Alls - % 0 - 50 - 100 0 - 50 - 100
CHARGE
R410A refrigerant Alls - lb 28.0 35.3
Oil compressor Alls - lb 3.5 3.5
SYSTEM SIDE EXCHANGER
Quantity Alls - 1.00 1.00
Water content Alls - dm 1.90 2.50
Hydraulic connection Alls - Ø
HYDRONIC KIT SYSTEM SIDE
Storage tank HA -
EXPANSION VASSEL
Expansion vassel HP-HA -
Expansion vassel calibration HP-HA - bar 1.50 1.50
PUMP
Imput power - - kW 0.75 1.50
Imput current
- 220-3-60 A 3.6 6.2
- 460-3-60 A 2.0 3.2
SAFETY VALVE
Safety valve - -
FAN
Quantity - - 2 2
Air flow - - cfm 8,240 7,946
Input current - A 2 2
Input power - - kW 0.6 0.6
SOUND DATA
Sound power - - 76.0 77.0
- - 44.0 45.0
DIMENSION
Height - - in 53 53
Width - - in 30 30
Depth - - in 69 69
Weight
H - lb 650 710
HP - lb 690 756
HA - lb 800 866
HEATING CONDITIONS
COOLING CONDITIONS
SOUND POWER
SOUND PRESSURE