EasyManuals Logo
Home>AERMEC>Chiller>ANL

AERMEC ANL User Manual

AERMEC ANL
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
EN
21.11 - 6755517_05
13
8. TECHNICAL DATA
TECHNICAL DATA MODELS POWER SUPPLY M.U. ANL100 ANL150
COOLING MODE
Cooling capacity Alls Alls ton 6.6 8.2
Total input power
H Alls kW 8.2 9.5
HP-HA Alls kW 9.0 11.0
Water flow rate Alls Alls gpm 15.7 19.5
Evaporator pressure drops H - ft HO 10.04 10.08
 HP-HA - ft HO 45.32 72.25
HEATING MODE
Heating capacity Alls Alls  94,755 111,850
Total input power
H Alls kW 8.3 9.6
HP-HA Alls kW 9.0 11.1
Water flow rate Alls Alls gpm 19.1 22.6
Evaporator pressure drops H - ft HO 14.71 11.87
 HP-HA - ft HO 40.22 70.08
ENERGY INDEX
EER
H Alls  9.57 10.33
HP-HA Alls  9.11 9.57
COP
H Alls  3.35 3.43
HP-HA Alls  3.18 3.16
 H Alls  16.38 17.71
ELECTRICAL DATA
Input current on
COOLING
H  A 31.40 36.70
H  A 17.10 19.64
HP-HA  A 34.26 42.51
HP-HA  A 18.66 22.75
Input current on
HEATING
H  A 31.59 37.05
H  A 17.21 19.83
HP-HA  A 34.45 42.86
HP-HA  A 18.76 22.93

H  A 168.4 193.2
H  A 82.4 95.3
HP-HA  A 171.4 198.8
HP-HA  A 83.9 98.1
MCA
H  A 47.4 55.7
H  A 24.3 29.9
HP-HA  A 50.4 61.3
HP-HA  A 25.8 32.7
MOP
H  A 60.0 75.0
H  A 30.0 40.0
HP-HA  A 60.0 80.0
HP-HA  A 30.0 40.0
HEATING CONDITIONS
 
 



COOLING CONDITIONS
 
 
 


 
 
 
 
SOUND POWER

-

SOUND PRESSURE





Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC ANL and is the answer not in the manual?

AERMEC ANL Specifications

General IconGeneral
BrandAERMEC
ModelANL
CategoryChiller
LanguageEnglish