EN
21.11 - 6755517_05
13
8. TECHNICAL DATA
TECHNICAL DATA MODELS POWER SUPPLY M.U. ANL100 ANL150
COOLING MODE
Cooling capacity Alls Alls ton 6.6 8.2
Total input power
H Alls kW 8.2 9.5
HP-HA Alls kW 9.0 11.0
Water flow rate Alls Alls gpm 15.7 19.5
Evaporator pressure drops H - ft HO 10.04 10.08
HP-HA - ft HO 45.32 72.25
HEATING MODE
Heating capacity Alls Alls 94,755 111,850
Total input power
H Alls kW 8.3 9.6
HP-HA Alls kW 9.0 11.1
Water flow rate Alls Alls gpm 19.1 22.6
Evaporator pressure drops H - ft HO 14.71 11.87
HP-HA - ft HO 40.22 70.08
ENERGY INDEX
EER
H Alls 9.57 10.33
HP-HA Alls 9.11 9.57
COP
H Alls 3.35 3.43
HP-HA Alls 3.18 3.16
H Alls 16.38 17.71
ELECTRICAL DATA
Input current on
COOLING
H A 31.40 36.70
H A 17.10 19.64
HP-HA A 34.26 42.51
HP-HA A 18.66 22.75
Input current on
HEATING
H A 31.59 37.05
H A 17.21 19.83
HP-HA A 34.45 42.86
HP-HA A 18.76 22.93
H A 168.4 193.2
H A 82.4 95.3
HP-HA A 171.4 198.8
HP-HA A 83.9 98.1
MCA
H A 47.4 55.7
H A 24.3 29.9
HP-HA A 50.4 61.3
HP-HA A 25.8 32.7
MOP
H A 60.0 75.0
H A 30.0 40.0
HP-HA A 60.0 80.0
HP-HA A 30.0 40.0
HEATING CONDITIONS
COOLING CONDITIONS
SOUND POWER
-
SOUND PRESSURE