28
19.3. HYDRAULIC CIRCUIT FOR INTERNAL AND EXTERNAL ANL "HA"
System: Chiller with plate heat exchanger
PH 7.5-9
Electric conductivity 10-500S/cm
Total hardness 4.5-8.5°dH
Temperature < 65°C
Oxygen content < 0.1 ppm
Max. glycol amount 50%
Phosphates (PO4) < 2ppm
Manganese (Mn) < 0.05 ppm
Iron (Fe) < 0.3 ppm
Alkalinity (HCO3) 70 - 300 ppm
Chloride ions (Cl-) < 50 ppm
Sulphate ions (SO4) < 50 ppm
Sulphide ion (S) none
Ammonium ions (NH4) none
Silica (SiO2) < 30ppm
COMPONENTS PROVIDED AS STANDARD
1 Plate heat exchanger
2 Water temperature probe
3 Dierential pressure switch
4 Pump
5 Expansion tank
6 Water lter
7 Storage tank
8 Air vent valve
9 Safety valve
10 Drain tap
HYDRAULIC COMPONENTS RECOMMENDED EXTERNAL TO UNIT
(RESPONSIBILITY OF THE INSTALLER)
5 Expansion tank
8 Air vent valve
11 Anti-vibration joints
12 Cut-o valve
13 Pressure gauge
Components recommendedUnits
7
9
2
2
6
4
5
5
1
10
11
11
12
12
8
8
13
13
PT