7.10 SETTING THE INSTALLATION OF THE REMOTE ROOM
TEMPERATURE PROBE (AMBIENT SENSOR)
Remote sensor
With
Without
OK Cancel
After accessing the Ambient sensor” function, you can specify whether or not to
enable the remote room temperature probe (for more information about this com-
ponent, refer to the installation manual). Select the required logic, then press “OK”
to conrm.
NOTE:
1. The T-remote room“ option in the “Ctrl.state“ function will only be available if
the room temperature sensor is enabled;
2. If the relative function is activated (paragraph "8.3 Activating/deactivating
the memory (On/o memory) p. 25"), the value of these parameters will
be stored in the memory and automatically reset after any possible voltage
failure.
7.11 SETTING THE AIR PURGING FUNCTION (AIR REMOVAL)
Air removal
Air
Water tank
O
OK Cancel
After accessing the Air removal” function, you can activate water circulation (in the
selected circuit) to eliminate any air from the circuit. Select the required logic, then
press “OK” to conrm.
NOTE:
1. This function can only be activated if the unit is switched O. In addition, this
function must be disabled before the unit can be switched On;
2. If the relative function is activated (paragraph "8.3 Activating/deactivating
the memory (On/o memory) p. 25"), the value of these parameters will
be stored in the memory and automatically reset after any possible voltage
failure.
7.12 SETTING THE PRE-HEATING PROCEDURE FOR
RADIANT PANELS (FLOOR DEBUG)
Start
Floor debug: On
Segments: 2
Period 1 temp: 25°C
Segment time: 12H
∆T of segment: 5°C
After accessing the “Floor debug” function, you can activate or deactivate any pos-
sible procedure for pre-heating the radiant panels. This procedure creates a heating
cycle during which the temperature is kept stable for a certain time (period), then
increased by a value equal to T indicated, and kept there for the next period. This
temperature increase and hold procedure will be repeated for the number of peri-
ods specied.
At the end, press the button at the top right to start (or interrupt) the pre-heating
cycle.
NOTE:
1. During the execution of this function, all other functions are disabled;
2. You are advised to use this function to gradually activate the heating function
via the radiant panels (this procedure should be carried out at the start of the
season);
3. If the relative function is activated (paragraph "8.3 Activating/deactivating
the memory (On/o memory) p. 25"), the value of these parameters will
be stored in the memory and automatically reset after any possible voltage
failure.
7.13 ACTIVATING THE DEFROST CYCLE (MANUAL DEFROST)
Manual defrost
On
O
OK Cancel
After accessing the "Manual defrost" function, you can activate or deactivate the
command for forced execution of a defrost cycle. Make your selection, then press
“OK” to conrm.
NOTE:
1. This function can only be activated if the unit is switched O;
2. The defrosting cycle is automatically interrupted if the defrosting temperature
rises above 20°C, or in any case after 10 minutes;
3. If the relative function is activated (paragraph "8.3 Activating/deactivating
the memory (On/o memory) p. 25"), the value of these parameters will
be stored in the memory and automatically reset after any possible voltage
failure.