22
ELECTRICAL DATA 208V360HZ  FAN J
ELECTRICAL DATA 230V360HZ  FAN J
208V-3-60Hz - Fan J
Units
Total consumption
L.R.A. F.L.A. MOP Recommended fuse Phases
Mod. Comp. Fan
NRB Vers. (n°) (n°) (A) (A) (A) (A) (n°)
0800
A 4 4 605 272 328 300 3
E 4 6 620 287 343 300 3
U 4 6 620 287 343 300 3
N 4 8 635 302 358 350 3
0900
A 4 4 780 313 387 350 3
E 4 6 795 328 402 400 3
U 4 6 795 328 402 400 3
N 4 8 810 343 417 400 3
1000
A 4 6 816 364 438 400 3
E 4 6 816 364 438 400 3
U 4 6 816 364 438 400 3
N 4 8 831 379 453 450 3
1100
A 4 6 929 389 475 450 3
E 4 8 944 404 490 450 3
U 4 8 944 404 490 450 3
N 4 10 959 419 505 500 3
1200
A 4 6 956 414 499 450 3
E 4 8 971 429 514 500 3
U 4 8 971 429 514 500 3
N 4 10 986 444 529 500 3
230V-3-60Hz - Fan J
Units
Total consumption
L.R.A. F.L.A. MOP Recommended fuse Phases
Mod. Comp. Fan
NRB Vers. (n°) (n°) (A) (A) (A) (A) (n°)
0800
A 4 4 578 267 323 300 3
E 4 6 593 282 338 300 3
U 4 6 593 282 338 300 3
N 4 8 608 297 353 350 3
0900
A 4 4 752 308 382 350 3
E 4 6 767 323 397 350 3
U 4 6 767 323 397 350 3
N 4 8 782 338 412 400 3
1000
A 4 6 786 359 433 400 3
E 4 6 786 359 433 400 3
U 4 6 786 359 433 400 3
N 4 8 801 374 448 400 3
1100
A 4 6 938 385 470 450 3
E 4 8 953 400 485 450 3
U 4 8 953 400 485 450 3
N 4 10 968 415 500 450 3
1200
A 4 6 1042 407 493 450 3
E 4 8 1057 422 508 500 3
U 4 8 1057 422 508 500 3
N 4 10 1072 437 523 500 3
L.R.A. Peak current from unit
F.L.A. Maximum current from unit
Earth Earth wire to connect to unit
IL Master switch