9. TECHNICAL DATA
Model 0800 0900 1000 1250 1400 1500 1650 1800
1
COOLING MODE
Cooling capacity A ton 51,71 58,45 65,31 82,72 94,63 106,64 113,01 120,35
Input power A kW 64,11 73,01 81,91 102,49 117,53 132,42 141,29 151,41
Water flow rate A gpm 123,84 139,98 156,42 198,11 226,65 255,4 270,65 288,24
Total pressure drops
SYSTEM SIDE
A PSI 3,92 4,35 3,19 3,48 3,63 4,06 4,06 4,21
Available static pressure
Low static pressure pump
A PSI 21,40 19,95 20,03 18,75 23,11 19,63 21,52 20,31
Available static pressure
High static pressure pump
A PSI 38,73 37,16 37,04 34,89 41,80 37,56 43,57 42,41
2
HEATING MODE
Heating capacity A BTU/h 738278 830351 928369 1178567 1338583 1498599 1594589 1689276
Input power A kW 70,91 79,71 87,11 111,92 126,32 140,72 149,92 158,92
Water flow rate A gpm 163,85 184,29 206,04 261,57 297,09 332,60 353,90 374,92
Pressure drops
SYSTEM SIDE VERS. 2 PIPES
A PSI 16,37 13,89 13,69 10,67 12,95 7,43 13,42 11,61
Pressure drops
DHW SIDE/SYSTEM SIDE
A PSI
33,26 30,37 29,62 24,82 29,56 22,62 35,70 33,91
ENERGY INDEX
EER A BTU/W 9,70 9,63 9,56 9,70 9,67 9,67 9,60 9,56
COP A W/W 3,05 3,05 3,12 3,09 3,11 3,12 3,12 3,12
1
COOLING CONDITIONS: AHRI STANDARD
System water outlet 6,7°C - 44,06°F
System water flow 0,043 l/s per kW
External air temperature 35°C - 95°F
2
HEATING CONDITIONS:
DHW / System water inlet 40°C - 104°F
DHW / System water outlet 45°C - 113°F
External air temperature d.b./w.b. 7/6°C - 44,6°F/42,8
1
DHW SIDE/SYSTEM SIDE
DHW side, production of domestic hot water, in 2-pipe systems.
System side, production of hot water, in 4-pipe systems.
13
INRP260HzTY. 1312. 5806717_03