26 21.05 - 6068956_00
NXP 0500 - 1650 2-PIPE SYSTEM / 4-PIPE SYSTEM
EN
L1 L2 L3
PHASE
EARTH (PE)
ELECTRIC DATA TABLE
The cable sections shown in the table are recommended for maximum lengths of 50 m.
dimension the appropriate line switch, the power supply line as well as the connection
to the earth wire and connection cables depending on:
• the length;
• the type of cable;
• the absorption of the unit and the physical location and also the environment
temperature.
NOTES:
MCA
MOP
SCCR
Pumps equipped versions: data on demand
ELECTRICAL DATA NXP 0500 0550 0600 0650 0700 0750 0800 0900 1000 1250 1400 1500 1650
Power supply 230V/3~/60Hz
Total input current in cooling mode A 93 91 102 112 127 140 186 196 209 238 264 303 341
Total input current in heating mode A 104 106 117 131 148 163 211 226 243 276 307 353 400
Total input current in recovery mode A 105 106 118 132 148 162 210 224 242 274 304 349 395
Total input current cooling + recovery mode A 105 107 118 132 149 162 211 225 243 275 306 352 398
LRA A 404 381 421 361 433 456 532 709 734 853 892 917 979
MCA A 125 131 136 142 182 218 237 278 314 340 362 417 466
MOP A 181 182 192 175 233 269 293 352 388 425 448 527 575
Recommended fuse A 175 175 175 175 225 250 250 350 350 400 400 500 500
Power supply 460V/3~/60Hz
Total input current in cooling mode A 42 41 46 51 57 63 84 89 95 108 120 137 154
Total input current in heating mode A 47 48 53 59 67 74 96 102 110 125 139 160 181
Total input current in recovery mode A 47 48 53 60 67 73 95 102 109 124 138 158 179
Total input current cooling + recovery mode A 48 48 53 60 67 74 95 102 110 124 138 159 180
LRA A 208 187 216 180 210 220 266 318 328 384 402 454 482
MCA A 62 67 72 79 89 98 115 124 132 158 181 209 234
MOP A 88 89 98 97 112 121 141 154 163 200 223 264 289
Recommended fuse A 80 80 90 90 110 110 125 150 150 200 200 250 250
Power supply 575V/3~/60Hz
Total input current in cooling mode A 32 32 36 39 44 49 65 68 73 83 92 105 119
Total input current in heating mode A 36 37 41 46 51 57 74 79 85 96 107 123 139
Total input current in recovery mode A 36 37 41 46 52 56 73 78 84 95 106 122 138
Total input current cooling + recovery mode A 37 37 41 46 52 57 73 79 85 96 107 123 139
LRA A 154 137 160 122 155 163 199 251 260 324 338 350 371
MCA A 56 53 58 57 73 87 103 105 107 130 150 183 212
MOP A 79 73 81 70 92 107 127 130 131 164 185 232 261
Recommended fuse A 75 70 80 70 90 100 125 125 125 150 175 225 250
Power supply 208V/3~/60Hz
Total input current in cooling mode A 102 101 113 124 140 155 205 217 232 263 292 335 378
Total input current in heating mode A 115 117 130 145 163 180 234 250 269 305 339 390 442
Total input current in recovery mode A 116 117 130 145 164 179 232 248 267 303 336 386 437
Total input current cooling + recovery mode A 116 118 130 146 164 180 233 249 268 304 338 389 440
LRA A 411 390 430 374 447 472 553 731 758 879 922 950 1019
MCA A 132 137 143 148 188 224 243 284 320 346 369 423 472
MOP A 188 188 198 181 240 275 299 358 394 431 454 533 582
Recommended fuse A 175 175 175 175 225 250 250 350 350 400 450 500 500