OPERATING RANGE
VED 030I 040I 130I 140I 230I 240I 330I 340I
Maximum water inlet temperature recommended °C 65
l/h 150 150 150 150 150 150 300 400
l/h 1500 1500 1500 1500 1500 1500 3000 4000
Minimum water flow rate
l/h 50 - 50 - 50 - 100 -
Maximum water flow rate
l/h 500 - 500 - 500 - 1000 -
The earth leakage current of several devic-
es placed under the same circuit breaker
is summed, therefore, we recommend
paying attention to the calibration value
of the circuit breaker and, if necessary,
consider splitting the installation in more
circuits, each of which protected by its
own circuit breaker.
VED 530I 540I 532I 541I 730I 740I 732I 741I
Maximum water inlet temperature recommended °C 65
l/h 300 300 300 300 300 300 300 300
l/h 3000 3000 3000 3000 4500 4500 4500 4500
Minimum water flow rate
l/h - - 200 100 - - 300 300
Maximum water flow rate
l/h - - 2000 1500 - - 2500 3000
21 23 25 27 31
15 3 3 3 3 3 3
17 3 3 3 3 3 3
3 3 3 3 3 3
21 6 5 4 3 3 3
23 - 8 7 6 5 5
If the fan coil runs continuously in cooling
mode in an environment with high relative
humidity, condensate may form on the air
flow. This condensate could drip onto the
floor and onto any underlying objects. To
prevent condensation phenomena on the
external structure of the appliance with the
fan running, the average water temperature
must not drop below the limits indicated in
the table. These limits depend on the tem-
perature and humidity conditions of the
room air. These limits refer to operation with
the fan running at minimum speed.
Condensation may form in the event the fan
is off for a prolonged period and cold water
flows in the coil;
In order to prevent air stratification in the
environment and thus, have better mixing,
the fan coil should not be supplied with
at a very high temperature can cause creak-
ing due to the heat expansion of the ele-
not cause damage to the unit unless the
maximum operating temperature is exceed-
ed.