EasyManua.ls Logo

AERMEC WMT21 - Main Configuration Parameters; Set Values

AERMEC WMT21
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
61
ENGLISHAPPENDIX A DEUTSCH ITALIANOFRANÇAISESPAÑOL
DFLT PAR. DESCRIPTION SET VALUES
0
P01
System type
0
2-pipes system
1
4-pipes system
2
Electric heater
3
Integrating
electric heater
0
P02
Heating/cooling
selection
0
Manual
1
Automatic
2
Remote
3
P03
Heating
regulation
1
Valves only
2
Fan only
3
Valves and fan
3
P04
Cooling
regulation
1
Valves only
2
Fan only
3
Valves and fan
0
P05
Fan output type
0
Proportional,
direct action
1
Proportional,
inverse action
2
3 speeds relays
2
P06
Heating output
type
0
Proportional,
direct action
1
Proportional,
inverse action
2
NC ON/OFF
valve
3
NO ON/OFF
valve
2
P07
Cooling output
type
0
Proportional,
direct action
1
Proportional,
inverse action
2
NC ON/OFF
valve
3
NO ON/OFF
valve
0
P08
Supply water
sensor input
0
Do not show
temperature
1
Show
temperature
2
Bi-metallic
contact
0
P09
De-stratication
0
Never
1
Cooling only
2
Heating only
3
Always
1
P10
On/Off state
at power up
1
Last
2
Always ON
3
Always OFF
0 P11
Room temperature
sensor
0
Internal
1
External
Table 1: Main conguration parameters (to set temperatures to Fahrenheit degrees see appendix A page 130).