29
automatically restart;
3Please contact with local dealer if error remains the same
after several reset.
Isolation Fault
1.PV(+) or PV(-) earthing
2Lightening
3Machine failure
1..Check PV(+) and PV(-) ground impedance make
sure impedance is more than 2MΩ;
2Please contact with after-sales if error remains the same
after several reset.
Current DC Offset
1.AC side incorrect wiring
2Electricity grid abnormal
3Machine failure
1.Disconnect the input/output switch, check the AC-side wiring
and reseat the plug to rule out bad contact.
2 After electricity grid returns to normal, the machine will
automatically restart;
3Please contact with local dealer if error remains the same
after several reset.
ENS Grid F Fault
1.AC side incorrect wiring
2Grid frequency abnormal
3Machine failure
1.Disconnect the input/output switch, check the AC-side wiring
and reseat the plug to rule out bad contact.
2 After electricity grid returns to normal, the machine will
automatically restart;
3Please contact with local dealer if error remains the same
after several reset.
ENS Grid V Fault
1.AC side incorrect wiring
2Grid voltage abnormal
3Machine failure
1.Disconnect the input/output switch, check the AC-side wiring
and reseat the plug to rule out bad contact.
2 After electricity grid returns to normal, the machine will
automatically restart;
3Please contact with local dealer if error remains the same
after several reset.
Relay 1/2 Fault
1.Machine failure
1.Please contact with local dealer if error remains the same
after several reset.
M Grid Freq Fault
1.Electricity gridfluctuations
2.Electricity gridFrequency
out of range
3.Machine failure
1.After electricity grid returns to normal, the machine will
automatically restart;
2Please contact with local dealer if error remains the same
after several reset.
Manual reset: disconnect the input/output switch in turn, wait until the display and LEDsdo not light up, then turn on
and off input/output switch.
Restart: Disconnect input and output switches in order, reconnect them after LCD and indicating lights go off.
If there is no display on the LCD, please check both AC and DC wiring.
If the input DC voltage is higher than start up voltage, the inverter still doesn’t work, please call local service.
If it is intended to replace the cable or open the enclosure lid, please call our service.
Under the low light conditions, the inverter may continuously start up and shut down. It is due to insufficient
power generated to operate the control circuits.