EasyManua.ls Logo

Aico Ei3018 - Unsuitable Locations for Installation

Aico Ei3018
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
In a room WITHOUT a fuel burning appliance
2.5 Unsuitable locations
Do not place the Alarm in any of the following areas:
In a bathroom or other areas where the Alarm may be exposed to water splashes, dripping or
condensation (e.g. above an electric kettle).
In very high or awkward areas where it may be difficult to reach the Alarm (for testing, hushing
etc.) or fit the screwdriver to release the Alarm from its mounting plate.
• Next to or directly above heaters or air conditioning vents, doors, windows, extractor fans or
anywhere that it would be affected by draughts.
Directly above a sink or cooker.
In an area where the temperature could drop below –10°C or rise above 40°C.
• Outside the building.
CO Alarm
about
1 to 2m
Fig.3
Wall mounted (Ei3018 only)
- At breather level (approx.. 1 to 2m above the
floor) so it is possible to view the three light
indicators.
WARNING: The Ei3028 Heat and Carbon
Monoxide Alarm is not suitable for wall
mounting

Related product manuals