14 | IXG Commercial Quick Start Programming Guide
IXG and IX Series Stations use SIF signaling to trigger outputs on IXW-MA(A) multi-purpose adaptors. This can 
be used to mirror outputs on the stations for door release or external signaling.
IXW-MA(A) Programming
Navigate to Network Settings, IP Address. Enter an IP address, subnet mask, and (optionally) a default gateway 
for the newly added adaptors. Click 
Save
.
Adding IXW-MA(A) to a System
Navigate to Site Settings, I/O Adaptor Registration. There will be a list of up to 99 adaptors. Place a check in the 
Enable column for each adaptor to be added. Click 
Save
.
The IXW-MA(A) itself does 
not need any programming 
in this section.
Conguring Stations for SIF Signaling
Navigate to Function Settings, SIF. For each station that will signal the IXW-MA(A), set SIF Functionality to 
Enable. Under the SIF Settings column, set the Program Type to 0100, enter the IP address of the IXW-MA(A) 
under IPV4, set the Destination Port to 65014, set SSL to Enabled, and Connection to Socket.
Scroll right to the Transmission Trigger section. For each station signaling the IXW-MA(A), check o 
Change Contact. Once these settings are congured, click 
Save
.