7-1
ELECTRICAL DATA
SM HJD DCI 1-A.1 GB
7. ELECTRICAL DATA
7.1 Single Phase Unit
Model HJD00 9 DCI HJD0 12 DCI HJD01 8 DCI HJD0 24 DCI
ZH05, CAV042-022, HP 1ylppuSrewoP
roodtuo oTroodni oTot detcennoC
Maximum Current 10A 13.5A 15.7A
Inrush Current \
(a)
35A 45 A <35A
Starting Current\
(b)
10A 13.5A 15.7A
A02A61rekaerB tiucriC
²mm 5.2 X3²mm 5.1 X3ylppuSrewoP
²mm 5.2 X4²mm 5.1 X4elbac gnitcennocretnI
(a) Inrush current is the current when power is up (charging the DC capacitors
at outdoor unit controller).
(b) Starting current is the current at compressor start up.
NOTE
Power wiring cord should comply with local lows and electrical
regulations requirements.
2
Model HJD009 DCI HJD012 DCI HJD018 DCI HJD024 DCI HJD030 DCI
Power Supply
Connected to
Maximum Current
Inrush Current \
(a)
Starting Current \ (b)
Circuit Breaker
Power Supply
Interconnection Cable
1 PH, 220-240VAC, 50HZ
To indoor To outdoor
10A 15A
4 X 1.5 mm²
45A
<15A
20A
3 X 2.5 mm²
4 X 2.5 mm²
35A
10A
16A
3 X 1.5 mm²