Technical data
CLH HPF 182 202 242 302 352
Power supply
V/ph/Hz
400/3/50
Number of circuits 22222
Number of steps 22223
Capacity control steps %
50/100 50/100 50/100 50/100 43-57/100
Refrigerant
Type R407C
Charge (1) kg 9.0 12.0 15.0 15.0, 15.0
Compressors
Type Scroll Scroll Scroll Scroll Scroll
Number 22222
Start-up type Direct
Evaporator
Type Plate type
Number 22222
Water flow rate
l/s
2.0 2.6 3.2 3.8 4.2
Pressure drop kPa 19.9 28.4 30.4 29.5 22.1
Minimum water content l 3.3 3.9 2.8 3.3 4.4
Condenser
Type Coil type (Al/Cu)
Hydraulic connections
Type Gas threaded male type
Inlet diameter inch 2” 2” 2” 2” 2”
Outlet diameter inch 2” 2” 2” 2” 2”
Weights
Basic unit kg 650 700 860 910 1010
Unit with single pump kg 682 732 892 942 1042
Unit with double pump kg 702 752 912 962 1062
Unit with tank and single pump kg 947 997 1157 1362 1552
Unit with tank and double pump kg 967 1017 1177 1382 1572
Dimensions
Length mm 2100 2100 2760 2760 3110
Width mm 1110 1110 1110 1110 1110
Height mm 1850 1850 1850 1850 1850
(1) Indicative value. Always refer to the value specified on the unit’s label.
Manuale CLS-CLH1 7.2.2005 10:17 Pagina 48

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Airwell Itelco-Clima CLS 182 STD and is the answer not in the manual?

Airwell Itelco-Clima CLS 182 STD Specifications

General IconGeneral
BrandAirwell
ModelItelco-Clima CLS 182 STD
CategoryChiller
LanguageEnglish

Related product manuals