PRODUCTION PARAMETERS
Operation logic. This allows you to configure the operation logic with which the control
relays of the production control board will work:
- Aerothermal (by default)
- 2 pipes
- 4 pipes
- RadianT (recommended for RadianT365 systems)
Important: The production control board (CCP) configuration parameters are only available in
AZX6CCPWSCC for Airzone Blueface master thermostat of system no.1.
Mode Demand
Control relays
O1 O2 O3 O4 O5 O6
Stop Off - - - -
- -
Cooling
Air ON - ON - - -
Radiant ON - - ON - -
Off - - - - - -
Heating
Air - ON - - ON -
Radiant - ON - - - ON
Off - - - - - -
Dry
On - - - - - -
Off - - - - - -
Ventilation
On - - - - - -
Off - - - -
- -
Mode Demand
Control relays
O1 O2 O3 O4 O5 O6
Stop Off - - - -
- -
Cooling
Air ON - ON - - -
Radiant ON - - ON - -
Off ON - - - - -
Heating
Air - ON - - ON -
Radiant - ON - - - ON
Off - ON - - - -
Dry
On ON - - - - -
Off ON - - - - -
Ventilation
On - - - - - -
Off - - - -
- -
1. Aerothermal
2. 2 pipes / 4 pipes
Note: In this configuration, the indoor unit will remain in Standby mode once comfort has
been reached in all zones.
Control relays