Nivel 1.- ACCESS CONTROL AND INFORMATION (tid)
26
Description
Units
Min
Def
Max.
P10
Configuring digital input 1
0= Off 1= Door contact 2= External alarm
3= Severe external alarm 4= Change Set Point 5= Continuous cycle act.
6= Remote defrost
0
0
6
P11
Configuring digital input 2
0= Off 1= Door contact 2= External alarm
3= Severe external alarm 4= change Set Point 5= Continuous cycle act.
6= Remote defrost
0
*
6
P12
Digital input polarity 1
0=Energised on closed contact, 1=Energised on open contact
0
1
1
P13
Digital input polarity 2
0=Energised on closed contact, 1=Energised on open contact
0
0
1
P14
Maximum start-up time after pump down (Page 17)
(Values between 1 and 9 seconds are not accepted) (0=Disabled)
(sec.)
0
0
120
P15
Maximum pump down time (Page 17) (0=Disabled)
(min.)
0
0
15
P22
Cold room light timer (Page 16)
(min.)
0
0
999
P23
Stop fans and compressor on opening door (Page 14) 0=No 1=Si
0
0
1
P24
Start up delay for fans and compressor with door open (Page 14)
(min.)
0
0
999
EP
Exit Level 1
Description
Units
Min
Def
Max.
L5
Access code (Password) (Pág 19)
0
0
99
PU
Program version (Information)
-
Pr
Program revision (Information)
-
EP
Exit Level 1
Level 2
Level 2
Default parameters according to models
Parameter
Modelos
P11
P6
P62
AKO-15690/1/2/3
0=Deactivated
1=Pump down
1=Alarm
AKO-15697
0=Deactivated
2= Same compressor status
1=Alarm
AKO-15699/699-1
2= External alarm
2= Same compressor status
1=Alarm
AKO-15690/1/2/3-EVC
0=Deactivated
0=Deactivated
4=Pump down
AKO-15697-EVC
0=Deactivated
0=Deactivated
2= Same compressor status
AKO-15699-EVC
2= External alarm
0=Deactivated
2= Same compressor status