Important: All monitoring station forwarding settings should be set up via Alarm.com Monitor Settings.
ETL Requirements
This device is certified to be used for fire and burglary
monitoring in residential applications only. When using
this device with ETL installations, the following
requirements apply:
• The system must use a 12V 7AH backup battery.
• The +12V red power cable from the SEM must be
wired directly to the +12V AUX terminal at the panel
instead of to the backup battery.
• The account must be configured to send a phone
test once every 30 days. This can be achieved by
either:
◦ Programming an auto phone test locally or
using the Remote Toolkit.
◦ Enabling Manual/Auto Tests on the account
Monitoring Settings page.
• The enclosure tamper should be tested once every
year by removing the enclosure cover and verifying
a tamper event is reported to Alarm.com
Important:
• This installation must be done in accordance with the National Electrical Code, ANSI/NFPA 70; Chapter 29 of the
National Fire Alarm and Signaling Code, ANSI/NFPA 72; the Standard for the Installation of Residential Fire
Warning Systems, CAN/ULC-S540; Canadian Electrical Code, Part I, Safety Standard for Electrical Installations,
CSA C22.1; Standard for the Installation, Inspection and Testing of Intrusion Alarm Systems, CAN/ULC S302; and
Standard for Signal Receiving Centre Intrusion Alarm Systems and Operations, CAN/ULC S301.
• If Ethernet is active, the broadband communication medium used between the protected property and
communications service provider shall be for the exclusive use of the protected property and is not to be shared
with other communications service provider subscribers.
Gateway LED reference
The enclosure gateway LEDs can be used to indicate communication errors, panel communication, network
communication, and signal strength.