EasyManua.ls Logo

Allen-Bradley 1756-EN2T - Environmental Specifications

Allen-Bradley 1756-EN2T
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ControlLogix EtherNet/IP Module 23
Rockwell Automation Publication 1756-IN603C-EN-P - April 2010
Environmental Specifications - 1756-EN2T
Attribute 1756-EN2T
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating
Cold)
IEC 60068-2-2 (Test Bd, Operating Dry
Heat)
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
0…60 °C (32…140 °F)
Temperature, nonoperating
EC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)
40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged
Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
50 g
Emissions
CISPR 11
Group 1, Class A
Immunity, ESD
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Immunity, radiated RF
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80%AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900
MHz
10V/m with 200 Hz 50% Pulse 100%AM at 1890
MHz
3V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
Immunity, EFT/B
IEC 61000-4-4
±2 kV at 5 kHz on Ethernet port
Immunity, surge transient
IEC 61000-4-5
±2 kV line-earth(CM) on Ethernet port