EasyManuals Logo
Home>Allen-Bradley>Control Systems>1756-EN2T

Allen-Bradley 1756-EN2T User Manual

Allen-Bradley 1756-EN2T
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
ControlLogix EtherNet/IP Module 23
Rockwell Automation Publication 1756-IN603C-EN-P - April 2010
Environmental Specifications - 1756-EN2T
Attribute 1756-EN2T
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating
Cold)
IEC 60068-2-2 (Test Bd, Operating Dry
Heat)
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
0…60 °C (32…140 °F)
Temperature, nonoperating
EC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)
40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged
Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
50 g
Emissions
CISPR 11
Group 1, Class A
Immunity, ESD
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Immunity, radiated RF
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80%AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900
MHz
10V/m with 200 Hz 50% Pulse 100%AM at 1890
MHz
3V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
Immunity, EFT/B
IEC 61000-4-4
±2 kV at 5 kHz on Ethernet port
Immunity, surge transient
IEC 61000-4-5
±2 kV line-earth(CM) on Ethernet port