12 Rockwell Automation Publication 1794-IN102D-EN-P - July 2018
FLEX I/O AC Digital Input Modules
Connecting Wiring for the 1794-IA8I
1. For 1794-TB2, 1794-TB3, or 1794-TB3S – Connect individual input
wiring to even-numbered terminals on the 0...15 row (A) as indicated in
the Wiring Connections for 1794-IA8I table.
For 1794-TBN – Connect individual input wiring to even-numbered
terminals 0...14 on the 16...33 row (B) as indicated in the Wiring
Connections for 1794-IA8I table.
Input 9 A-9 C-9 C-44
Input 10 A-10 B-10 C-45
Input 11 A-11 C-11 C-46
Input 12 A-12 B-12 C-47
Input 13 A-13 C-13 C-48
Input 14 A-14 B-14 C-49
Input 15 A-15 C-15 C-50
120V AC L1
Power terminals C-34 to C-51 (C-34 and C-51 on 1794-TBN) are internally connected
together. Connect 120V AC L1 to C-34.
120V AC L2
Common terminals B-16 to B-33 (B-16 and B-33 for 1794-TBN) are internally connected
together. Connect 120V AC common L2 to terminal B-16.
(1) When using the 1794-TBN, an external terminal strip is needed to connect the 120V AC power connections.
Terminal Base Wiring for 1794-IA16
Input
Input Terminal
1794-TB3, 1794-TB3S
Input Terminal
1794-TBN
120V AC Supply (L1)
(1)