EasyManua.ls Logo

Allen-Bradley CompactLogix 1769-L23E-QB1B - HSC Single-ended Encoder Wiring Diagram

Allen-Bradley CompactLogix 1769-L23E-QB1B
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CompactLogix Controller 25
Rockwell Automation Publication 1769-IN082C-EN-P - February 2013
HSC Single-ended Encoder Wiring Diagram
(1) Refer to your encoder manual for proper cable type. The type of cable used should be twisted-pair, individually shielded cable with a maximum
length of 300 m (1000 ft.).
(2) External resistors are required if they are not internal to the encoder. The pull-up resistor (R) value depends on the power supply value. The table
below shows the maximum resistor values for typical supply voltages. To calculate the maximum resistor value, use this formula:
Where:
R = maximum pull-up resistor value
VDC = power supply voltage
Vmin = 2.6V DC
Imin = 6.8 mA
The minimum resistor (R) value depends on the current sinking capability of the encoder. Refer
to your encoder’s documentation for more information.
Power Supply Voltage (V DC) Maximum Pull-up Resistor Value (R)
(1)
(1) Resistance values may change, depending upon your application.
5V DC 352
12V DC 1382
24V DC 3147
A
B
Z
A1(+)
A1(–)
B1(+)
B1(–)
Z1(+)
Z1(–)
GND
VS
+VDC
COM
R
(2)
Cable
(1)
Power
Supply
Allen-Bradley
845H Series
Single-ended
Encoder
Shield/housing
Connect only if housing is electronically
isolated from the motor and ground.
Shield
Inputs
Earth
R
V
DC Vmin
Imin
--------------------------------------=
Allen-Bradley Parts

Related product manuals