12 Rockwell Automation Publication SAFETY-AT125C-EN-P - February 2022
Enabling Switch with an Integrated Safety Controller and a POINT Guard I/O Safety Module Safety Function Application Technique
For controller logic that you can download to your controller, see the attached ACD file.
Falling Edge Reset
ISO 13849-1 stipulates that instruction reset functions must occur on falling edge signals. To comply with this requirement, a One Shot Falling
(OSF) instruction is used on the reset rung. Then, the OSF instruction Output Bit tag is used as the reset bit for the STO output rung.
O1
FP
Dual Channel Input Stop
DCS
Zone1_Door
Safety Function
SAFETY GATE
Input Type
EQUIVALENT - ACTIVE HIGH
Discrepancy Time (Msec)
500
Restart Type
AUTOMATIC
Cold Start Type
AUTOMATIC
Channel A
AENT:1:I.Pt00Data
0
Channel B
AENT:1:I.Pt01Data
0
Input Status
AENT:1:I.CombinedInputStatus
0
Reset
AENT:1:I.Pt05Data
0
DCS
O1
FP
Dual Channel Input Start
DCSRT
Zone1_Enable_Pendant
Safety Function
ENABLE PENDANT
Input Type
EQUIVALENT - ACTIVE HIGH
Discrepancy Time (Msec)
250
Enable
Slow_Machine_Mode
0
Channel A
AENT:1:I.Pt02Data
0
Channel B
AENT:1:I.Pt03Data
0
Input Status
AENT:1:I.CombinedInputStatus
0
Reset
AENT:1:I.Pt05Data
0
DCSRT
AENT:1:I.Pt04Data
SB
OB
One Shot Falling
Storage Bit
Wrk_Zone1_OSF
Output Bit
Wrk_Zone1_FallingEdge
OSF
Wrk_Zone1_FallingEdge
Door_OK
Zone1_Door.O1
/
Zone1_K1K2.FP
Door_OK
Door_OK
Zone1_Enable_Pendant.O1
Energize_K1K2
O1
O2
FP
Configurable Redundant Output
CROUT
Zone1_K1K2
Feedback Type
NEGATIVE
Feedback Reaction Time (Msec)
500
Energize_K1K2
0
Feedback 1
AENT:1:I.Pt07Data
0
Feedback 2
AENT:1:I.Pt07Data
0
Input Status
AENT:1:I.CombinedInputStatus
0
Output Status
AENT:2:I.CombinedOutputStatus
0
Reset
AENT:1:I.Pt05Data
0
CROUT
Zone1_K1K2.O1 Zone1_K1K2.O2 AENT:2:O.Pt00Data
AENT:2:O.Pt01Data