PanelView Component HMI Terminals     9
Publication 2711C-IN001H-EN-P - July 2014
Install the Terminal
Before installing the terminal in a panel, review minimum clearances, panel guidelines, panel cutout 
dimensions, and product dimensions.
Minimum Spacing
Plan for adequate space around the terminal, inside the enclosure, for ventilation and cabling. Consider heat 
produced by other devices in the enclosure. The ambient temperature around the terminal must be 0…50 °C 
(32…122 °F). 
 
Mounting Angle
You can mount the terminal vertically against the panel, or tilted forward or backwards, up to a 45° angle. For 
mounting angles greater than 45°, the operating temperature is restricted to 40 °C (104 °F). 
Panel Guidelines
Supporting panels must be at least 16 gauge to provide proper sealing against water and dust and to provide 
proper support. The panel surface must be flat and free of imperfections to maintain an adequate seal and 
NEMA Type ratings.
PanelView Component  Top Bottom Sides Back
C200 Function Key
C300 Touch
51 mm (2 in.) 102 mm (4 in.) 25 mm (1 in.) 13 mm (0.5 in.)
C200 and C300 Keypad
C600 Touch
C400 Touchscreen and function 
keys
51 mm (2 in.)
C1000 Touch 25 mm (1 in.)
WARNING: When you insert or remove the SD Card while power is on, an electrical arc 
can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
The minimum spacing requirements are sufficient for connecting cables and inserting or 
removing a memory card. Plan for additional clearance if using the USB host port on the 
back of the unit.