62 Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 2 Start Up
P040 [Autotune] 0/2 0 = “Ready/Idle
1 = “Static Tune
2 = “Rotate Tune”
0
Enables a static (not spinning) or dynamic (motor
spinning) autotune.
P041 [Accel Time 1] 0.00/600.00 s 0.01 s 10.00 s
Sets the time for the drive to accel from 0 Hz to
[Maximum Freq].
P042 [Decel Time 1] 0.00/600.00 s 0.01 s 10.00 s
Sets the time for the drive to decel from [Maximum
Freq] to 0 Hz.
P043 [Minimum Freq] 0.00/500.00 Hz 0.01 Hz 0.00 Hz
Sets the lowest frequency the drive outputs.
P044 [Maximum Freq] 0.00/500.00 Hz 0.01 Hz 60.00 Hz
Sets the highest frequency the drive outputs.
P045 [Stop Mode] 0/11 0 = “Ramp, CF”
(1)
1=Coast, CF
(1)
2 = “DC Brake, CF”
(1)
3 = “DCBrkAuto,CF”
(1)
4=Ramp
5=Coast
6=DC Brake
7=DC BrakeAuto
8=Ramp+EM B,CF
(1)
9=Ramp+EM Brk
10 = “PointStp,CF”
(1)
11 = “PointStop
0
Stop command for normal stop.
Important: I/O Terminal 01 is always a stop input.
The stopping mode is determined by the drive
setting.
Important: The drive is shipped with a jumper
installed between I/O Terminals 01 and 11. Remove
this jumper when using I/O Terminal 01 as a stop or
enable input.
(1) Stop input also clears active fault.
P046,
P048,
P050
[Start Source 1] 1/5 1 = “Keypad”
(1)
2 = “DigIn TrmBlk”
(2)
3 = “Serial/DSI”
4 = “Network Opt”
5 = “Ethernet/IP”
(3)
P046 = 1
P048 = 2
P050 = 3 (PowerFlex 523)
5 (PowerFlex 525)
Sets the default control scheme used to start the
drive unless overriden by P048 [Start Source 2] or
P050 [Start Source 3].
(1) When active, the Reverse key is also active unless
disabled by A544 [Reverse Disable].
(2) If “DigIn TrmBlk” is selected, ensure that the digital
inputs are properly configured.
(3) Setting is specific to PowerFlex 525 drives only.
P047,
P049,
P051
[Speed Reference1] 1/16 1 = “Drive Pot”
2=Keypad Freq
3=Serial/DSI
4=Network Opt
5 = “0-10V Input”
6 = “4-20mA Input”
7=Preset Freq
8 = “Anlg In Mult”
(1)
9=MOP
10 = “Pulse Input”
11 = “PID1 Output”
12 = “PID2 Output”
(1)
13 = “Step Logic”
(1)
14 = “Encoder”
(1)
15 = “Ethernet/IP”
(1)
16 = “Positioning”
(1)
P047 = 1
P049 = 5
P051 = 3 (PowerFlex 523)
15 (PowerFlex 525)
Sets the default speed command of the drive unless
overridden by P049 [Speed Reference2] or P051
[Speed Reference3].
(1) Setting is specific to PowerFlex 525 drives only.
P052 [Average kWh Cost] 0.00/655.35 0.01 0.00
Sets the average cost per kWh.
P053 [Reset To Defalts] 0/3 0 = “Ready/Idle
1 = “Param Reset”
2 = “Factory Rset”
3 = “Power Reset”
0
Resets parameters to their factory defaults values.
After a Reset command, the value of this parameter
returns to zero.
= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.
No. Parameter Min/Max Display/Options Default
PF 525

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 520 Series and is the answer not in the manual?

Allen-Bradley PowerFlex 520 Series Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 520 Series
CategoryDC Drives
LanguageEnglish

Related product manuals