EasyManua.ls Logo

Allen-Bradley PowerFlex 70 - Output Contactor Precaution

Allen-Bradley PowerFlex 70
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English-10 PowerFlex 70 Adjustable Frequency AC Drive Quick Start
Step 5 Program the Drive – Parameter Files & Groups
Inputs & Outputs
File J
Communication
File H
Utility
File E
Dynamic Control
File D
Speed Command
File C
Motor Control
File B
Monitor
File A
Metering
Drive Data
Motor Data
Torq Attributes
Volts per Hertz
Speed Feedback*
Spd Mode & Limits
Speed References
Discrete Speeds
Speed Trim
Slip Comp
Process PI
Speed Regulator*
Ramp Rates
Load Limits
Stop/Brake Modes
Restart Modes
Power Loss
Direction Config
HIM Ref Config
MOP Config
Drive Memory
Diagnostics
Faults
Alarms
Comm Control
Masks & Owners
Datalinks
Security*
Analog Inputs
Analog Outputs
Digital Inputs
Digital Outputs
*Enhanced Control Only.
Frequently Used Parameters
MOTOR CONTROL (File B)
Motor Data
041 [Motor NP Volts]
Set to the motor nameplate rated volts.
Default:
Min/Max:
Units:
Drive Rating Based
0.0/[Rated Volts]
0.1 VAC
042 [Motor NP FLA]
Set to the motor nameplate rated full load
amps.
Default:
Min/Max:
Units:
Drive Rating Based
0.0/[Rated Amps] × 2
0.1 Amps
047
048
045 [Motor NP Power]
Set to the motor nameplate rated power.
Default:
Min/Max:
Units:
Drive Rating Based
0.00/100.00
0.00/412.48
0.01 kW/HP
See [Mtr NP Pwr Units]
046
046 [Mtr NP Pwr Units]
Selects the motor power units to be used.
Default:
Options: 0
1
Drive Rating Based
“Horsepower”
“kiloWatts”
047 [Motor OL Hertz]
Selects the output frequency below
which the motor operating current is
derated. The motor thermal overload will
generate a fault at lower levels of current.
Default:
Min/Max:
Units:
Motor NP Hz/3
0.0/500.0 Hz
0.1 Hz
042
220
Torq Attributes
053 [Torque Perf Mode]
Sets the method of motor torque
production.
Default:
Options:
0
0
1
2
3
“Sensrls Vect”
“Sensrls Vect”
“SV Economize”
“Custom V/Hz”
“Fan/Pmp V/Hz”
062
063
069
070
[Motor Cntl Sel]
Sets the method of motor control used in
the drive.
Important: “FVC Vector” mode requires
autotuning of the motor, both coupled
and uncoupled to the load.
(1)
Enhanced firmware 2.001 & later.
Default:
Options:
0
0
1
2
3
4
“Sensrls Vect”
“Sensrls Vect”
“SV Economize”
“Custom V/Hz”
“Fan/Pmp V/Hz”
“FVC Vector”
(1)
32
E C
Standard