EasyManua.ls Logo

Allen-Bradley PowerFlex 70 - Page 8

Allen-Bradley PowerFlex 70
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English-8 PowerFlex 70 Adjustable Frequency AC Drive Quick Start
I/O Wiring Examples
Input/Output Connection Example
(3)
Related
Param.
Potentiometer
(1)
10k Ohm Pot.
Recommended
(2k Ohm minimum)
Joystick
(1)
±10V Input -
100k ohm input
impedance
[Speed Ref A Sel] = “Analog In 1” 090
to
095
320
to
327
361
to
366
Potentiometer Joystick
Analog Input
Bipolar:
±10V
Unipolar:
0 to +10V, 100k
ohm impedance
4-20 mA, 100 ohm
impedance
[Speed Ref A Sel] = “Analog In 2”
Bipolar
(1)
Unipolar (Voltage) Unipolar (Current)
Analog/Digital
Output
0 to +10V Output -
Can drive a 2k
Ohm load (25 mA
short circuit current
limit)
Analog Output Digital N.O. / N.C. Output 341
to
344
380
to
387
2 Wire Control
(2)
-
Non-Reversing
Requires 2-wire
functions only
([Digital In1 Sel]).
Using 3-wire selec-
tions will cause a
type 2 alarm.
24V DC Input
(4)
: [Digital In2 Sel] = “Run” 361
to
366
Internal Supply External Supply
3 Wire Control
Requires 3-wire
functions only
([Digital In1 Sel]).
Using 2-wire selec-
tions will cause a
type 2 alarm.
24V DC Input
(4)
: [Digital In1 Sel] = “Stop – CF”, [Digital In2 Sel] = “Start”
Internal Supply External Supply
(1)
Refer to the Attention statement on page 2 for important bipolar wiring information.
(2)
Important: Programming inputs for 2 wire control deactivates all HIM Start buttons.
(3)
Examples show hardware wiring only. Refer to page 7 for parameters that must be adjusted.
(4)
If desired, a User Supplied 24V DC power source can be used. Refer to the “External” example.
14
15
22
10
18
19
22
Com
Power Source
-10V +10V
18
19
+
18
19
Common
+
20
21
Common
+
+
22
23
11
12
13
24
25
26
Power
Source
or
2
7
8
9
Stop-Run
+24V Common
2
8
Stop-Run
1
2
7
8
9
Stop
Start
+24V Common
1
2
8
Stop
Start

Other manuals for Allen-Bradley PowerFlex 70