Publication 20D-IN027A-EN-P
Frame
Voltage
Code
Current
Rating
Factory Default Jumper Settings
Power Source Type
MOV/Input Filter
Caps
(1)(2)
DC Bus Common
Mode Caps
6 B
C
D
H
J
N
P
R
All Two green/yellow
wires connected
to Power Terminal
Block “PE”
Green/yellow wire
to CM Cap Board
is connected to
Power Terminal
Block “PE”
Solid Ground
1. The green/yellow CM Cap jumper wire
should be connected to “PE.”
2. The MOV/Input Filter Cap jumper wires
should be connected to “PE.”
Non-Solid Ground
1. The green/yellow CM Cap jumper wire
should be insulated from ground. If
necessary, remove the jumper wire
from “PE” and insulate/secure it to
guard against unintentional contact
with chassis or components.
Important: Do Not Remove/
Disconnect the larger green/yellow
wire.
2. MOV/Input Filter Cap jumper wires
should be insulated from ground. If
necessary, remove the jumper wires
from “PE” and individually insulate/
secure each jumper wire to guard
against unintentional contact with
chassis or components.
E
F
T
W
All Two green/yellow
wires connected
to Power Terminal
Block “PE” and
chassis
Green/yellow wire
to CM Cap Board
is connected
to
Power Terminal
Block “PE”
Solid Ground
1. The green/yellow CM Cap and MOV
jumper wires should be connected to
“PE.”
2. The Input Filter Cap jumper wire (top
right) should be connected to chassis
ground with a metal screw. Verify. If
necessary, remove the nylon screw/
spacer and insert a metal M5 x 10
screw. Torque to 3.2 N•m (28 lb•in).
Non-Solid Ground
1. The green/yellow CM Cap and MOV
jumper wires should be insulated from
ground. If necessary, remove them
from “PE” and individually insulate/
secure each jumper wire to guard
against unintentional contact with
chassis or components. Important: Do
Not Remove/Disconnect the larger
green/yellow wire.
2. The Input Filter Cap jumper wire (top
right) should be insulated from ground
with a nylon screw/spacer. Verify. If
necessary, remove the metal screw
and insert a M5 x 15 nylon screw/
spacer.
(1)
AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2)
When removing MOV’s, the input filter capacitor must also be removed.
DC–DC+BR1BR2
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
PS+
PS–
USE 75 C
COPPER WIRE
ONLY
TORQUE
52 IN-LB
(6 N-M)
U
T1
V
T2
W
T3
R
L1
S
L2
INPUTOUTPUT
T
L3
PE PE
Optional
Communications
Module
PE PE
MOV
Input Filter Cap
CM Cap
DO NOT
REMOVE
MOV
DC–DC+BR1BR2
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
PS+
PS–
USE 75 C
COPPER WIRE
ONLY
TORQUE
52 IN-LB
(6 N-M)
U
T1
V
T2
W
T3
R
L1
S
L2
INPUTOUTPUT
T
L3
PE PE
Optional
Communications
Module
Input Filter Cap
PE PE
MOV
CM Cap
DO NOT
REMOVE
MOV