114 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
Frame Voltage
Class
ND/HD
Rating
(Amps)
Frequency
(kHz)
(1)
(1) Not all frequencies can be run on all drives.
Ambient Temp (C)
(2)
(2) Ambient Temp / Max. Surrounding Air Temperature is the air temperature surrounding the drive module. Rated temperature is 40/40 C (ND/HD) for 400V class drive and 35/35 C (ND/HD) for 600V class drive.
Derate
(2)
13 400 1450/1200 PWM 50 35 20
1.5 1291 1591 1809
2.0 1236 1518 1727
4.0 882 1145 1327
6.0 709 936 1100
8.0 582 782 927
10.0 491 664 791
600 1180/1030 PWM 50 35 20
1.5 945 1241 1457
2.0 864 1180 1374
4.0 564 786 945
6.0 427 600 736
8.0 336 482 600
10.0 273 395 500
Frame Voltage
Class
ND/HD
Rating
(Amps)
Frequency
(kHz)
(1)
(1) Not all frequencies can be run on all drives.
Ambient Temp (C)
(2)
(2) Ambient Temp / Max. Surrounding Air Temperature is the air temperature surrounding the drive module. Rated temperature is 30/30 C (ND/HD).
Derate
(2)
14 600 2250/1900 PWM 50 35 20
1.5 1803 2366 2778
2.0 1647 2167 2620
4.0 1075 1499 1803
6.0 815 1144 1404
8.0 641 919 1144
10.0 520 754 953
20
25
30
35
40
45
50
55
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
Iout (Amps)
1.5 kHz
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
Max. Surrounding Air Temperature °C
20
25
30
35
40
45
50
55
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
Iout (Amps)
1.5 kHz
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
Max. Surrounding Air Temperature °C
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
Iout (Amps)
1.5 kHz
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
Max. Surrounding Air Temperature °C